PLSED309039EN PM1000 Series Power Meters
08/2010 Chapter 6 Data Communication
© 2010 Schneider Electric. All rights reserved.
53
Data Address
The PM1200 power meter supports the transfer of whole block and also of
individual data values (two registers are used for storing single data value).
In the transfer of individual data values, it treats two registers as an object
with the starting address (e.g., 3900) considered as the object name. This
enables you to transfer required data values for energy management.
In the transfer of the whole block, it basically treats each block as an object
with the starting address (e.g.,3000) considered as the object name. This
enables fast block transfers, since energy management usually requires a
block of related readings for the same point of time. This method also
eliminates time-skew within readings of that block.
The device address, block start address, number of registers, must be
configured to suit the power meter. You must also make the related
SCADA settings for polling priority, logging, and viewing the data. Refer
your SCADA software instructions to learn how to do this.
Individual Parameter Address
Function Code: 03 Read
No scaling required
Read as block or individual parameters
Table 6-4: Individual parameter address
Parameter
Description
Address
Type
PM1200
Metering
Metering - Current
A
Current average
3913
Float
A1
Current, phase 1
3929
Float
A2
Current, phase 2
3943
Float
A3
Current, phase 3
3957
Float
Metering Voltage
VLL
Line to line average voltage
3909
Float
VLN
Line to neutral voltage
3911
Float
V12
Voltage phase 1 to phase 2
3925
Float
V23
Voltage phase 2 to phase 3
3939
Float
V31
Voltage phase 3 to phase 1
3953
Float
V1
Voltage phase 1 to neutral
3927
Float
V2
Voltage phase 2 to neutral
3941
Float
V3
Voltage phase 3 to neutral
3955
Float
Metering - Power
W
Active power, total
3903
Float
W1
Active power, phase 1
3919
Float
W2
Active power, phase 2
3933
Float
W3
Active power, phase 3
3947
Float
VAR
Reactive power, total
3905
Float
VAR1
Reactive power, phase 1
3921
Float
VAR2
Reactive power, phase 2
3935
Float
VAR3
Reactive power, phase3
3949
Float
VA
Apparent power, total
3901
Float
VA1
Apparent power, phase 1
3917
Float
VA2
Apparent power, phase 2
3931
Float
VA3
Apparent power, phase 3
3945
Float
Metering Power Factor
PF
Power factor average
3907
Float
PF1
Power factor, phase 1
3923
Float
PF2
Power factor, phase 2
3937
Float
PF3
Power factor, phase 3
3951
Float