PLSED309039EN PM1000 Series Power Meters
08/2010 Chapter 6 – Data Communication
© 2010 Schneider Electric. All rights reserved.
Data Address
The PM1200 power meter supports the transfer of whole block and also of
individual data values (two registers are used for storing single data value).
In the transfer of individual data values, it treats two registers as an object
with the starting address (e.g., 3900) considered as the object name. This
enables you to transfer required data values for energy management.
In the transfer of the whole block, it basically treats each block as an object
with the starting address (e.g.,3000) considered as the object name. This
enables fast block transfers, since energy management usually requires a
block of related readings for the same point of time. This method also
eliminates time-skew within readings of that block.
The device address, block start address, number of registers, must be
configured to suit the power meter. You must also make the related
SCADA settings for polling priority, logging, and viewing the data. Refer
your SCADA software instructions to learn how to do this.
Individual Parameter Address
Function Code: 03 Read
No scaling required
Read as block or individual parameters
Table 6-4: Individual parameter address
Line to line average voltage
Voltage phase 1 to phase 2
Voltage phase 2 to phase 3
Voltage phase 3 to phase 1
Voltage phase 1 to neutral
Voltage phase 2 to neutral
Voltage phase 3 to neutral