BBV46385
www.schneider-electric.com
2354235 11/2008
Altivar 312
Variable speed drives
for asynchronous motors
Programming manual
06/2010
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Zobrazit stránku 0
1 2 3 4 5 6 ... 125 126

Shrnutí obsahu

Strany 1 - Altivar 312

BBV46385 www.schneider-electric.com2354235 11/2008Altivar 312Variable speed drivesfor asynchronous motorsProgramming manual06/2010Courtesy of Steven

Strany 2

10 BBV46385 06/2010Setup - Preliminary RecommendationsBefore powering up the driveBefore configuring the driveStart-upNote: When factory settings ap

Strany 3 - Contents

100 BBV46385 06/2010[MONITORING] (SUP-) menuThe parameters can be accessed with the drive running or stopped.On the optional remote display terminal

Strany 4 - CAUTION

BBV46385 06/2010 101[MONITORING] (SUP-) menuCode Description Variation rangeLFrM [HMI Frequency ref.]0 to 500 HzgFrequency reference for control via

Strany 5

102 BBV46385 06/2010[MONITORING] (SUP-) menuCode Description Variation rangeLFtM [Last fault occurred]bLFCFFCFICnFCOFCrFEEFEPFIF1IF2IF3IF4LFFnOFObFO

Strany 6

BBV46385 06/2010 103[MONITORING] (SUP-) menuCode Description Variation rangeCOdM [PIN code 1]0FFOn8888Enables the drive configuration to be protecte

Strany 7 - Documentation structure

104 BBV46385 06/2010[MONITORING] (SUP-) menuCode Name/Description Adjustment rangeFactory settingLIA-b [LOGIC INPUT CONF.]LI1ALI2ALI3ALI4ALI5ALI6ACa

Strany 8 - Software enhancements

BBV46385 06/2010 105Migration ATV31 - ATV312The ATV312 is compatible with the ATV31.To retrieve the configuration of the ATV31, simply transfer the

Strany 9 - PROGRAMMING

106 BBV46385 06/2010Diagnostics and troubleshootingDrive does not start, no code displayed• If the display does not light up, check the power supply

Strany 10 - Line contactor

BBV46385 06/2010 107Diagnostics and troubleshooting (continued)Fault detection codes which require a power reset after the fault is cleared (continu

Strany 11 - Factory configuration

108 BBV46385 06/2010Diagnostics and troubleshooting (continued)Fault detection codes that can be reset with the automatic restart function after the

Strany 12 - Basic functions

BBV46385 06/2010 109Diagnostics and troubleshooting (continued)Fault detection codes that are reset as soon as their cause disappearsCode Name Proba

Strany 13

BBV46385 06/2010 11Factory configurationFactory settingsThe Altivar 312 is factory-set for the most common operating conditions:• Display: drive rea

Strany 14 - 14 BBV46385 06/2010

110 BBV46385 06/2010Diagnostics and troubleshooting (continued)Fault detection codes displayed on the ATV12 remote display terminal(1) FlashingCode

Strany 15 - Description of the terminal

BBV46385 06/2010 111Index of functions[+/- SPEED]77[2/3 wire control]47[ACCESS LEVEL]58[Analog./logic output]48[Auto DC injection]69[Automatic resta

Strany 16 - 16 BBV46385 06/2010

112 BBV46385 06/2010Index of parameter codes and customer settingsCode Page Name Unit Value/Possible functionFactorysettingCustomersettingAC23264[Ac

Strany 17 - BBV46385 06/2010 17

BBV46385 06/2010 113Index of parameter codes and customer settingsCode Page Name Unit Value/Possible functionFactorysettingCustomersettingCCS 60 [Cm

Strany 18 - Subsequent power-ups

114 BBV46385 06/2010Index of parameter codes and customer settingsCode Page Name Unit Value/Possible functionFactory settingCustomersettingCOL95[CAN

Strany 19

BBV46385 06/2010 115Index of parameter codes and customer settingsCode Page Name Unit Value/Possible functionFactorysettingCustomersettingdSP78[-Spe

Strany 20 - [PI regulator]

116 BBV46385 06/2010Index of parameter codes and customer settingsCode Page Name Unit Value/Possible functionFactorysettingCustomersettingFr12958[Re

Strany 21 - Compatibility of functions

BBV46385 06/2010 117Index of parameter codes and customer settingsCode Page Name Unit Value/Possible functionFactorysettingCustomersettingInr 63 [Ra

Strany 22

118 BBV46385 06/2010Index of parameter codes and customer settingsCode Page Name Unit Value/Possible functionFactorysettingCustomersettingLEt 93 [Ex

Strany 23 - BBV46385 06/2010 23

BBV46385 06/2010 119Index of parameter codes and customer settingsCode Page Name Unit Value/Possible functionFactorysettingCustomersettingnSP 42 [Ra

Strany 24 - 24 BBV46385 06/2010

12 BBV46385 06/2010Basic functionsDrive thermal protectionFunctions:Thermal protection by PTC probe fitted on the heatsink or integrated in the powe

Strany 25 - Modbus control word bits

120 BBV46385 06/2010Index of parameter codes and customer settingsCode Page Name Unit Value/Possible functionFactorysettingCustomersettingPr4 82 [4

Strany 26 - Checklist

BBV46385 06/2010 121Index of parameter codes and customer settingsCode Page Name Unit Value/Possible functionFactorysettingCustomersettingr1 49 [R1

Strany 27 - Programming

122 BBV46385 06/2010Index of parameter codes and customer settingsCode Page Name Unit Value/Possible functionFactorysettingCustomersettingrPS 64 [Ra

Strany 28

BBV46385 06/2010 123Index of parameter codes and customer settingsCode Page Name Unit Value/Possible functionFactorysettingCustomersettingSFr4044[Sw

Strany 29

124 BBV46385 06/2010Index of parameter codes and customer settingsCode Page Name Unit Value/Possible functionFactorysettingCustomersettingStP 96 [Un

Strany 30

BBV46385 06/2010 125Index of parameter codes and customer settingsCode Page Name Unit Value/Possible functionFactorysettingCustomersettingtnL 95 [Au

Strany 31 - [SPEED REFERENCE] (rEF-) menu

ATV312_programming_manual_EN_BBV46385_0206/2010Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650

Strany 32 - [SETTINGS] (SEt-) menu

BBV46385 06/2010 13Basic functionsMotor thermal protectionFunction:Thermal protection by calculating the I2t.The protection takes account of self-co

Strany 33

14 BBV46385 06/2010Remote display terminal option, ATV31This terminal is a local control unit which can be mounted on the door of the wall-mounted o

Strany 34

BBV46385 06/2010 15Remote graphic display terminal option, ATV61/ATV71Description of the terminalThanks to the screen size of this graphic display t

Strany 35

16 BBV46385 06/2010Remote graphic display terminal option, ATV61/ATV71 (continued)Powering up the graphic display terminal for the first timeWhen po

Strany 36

BBV46385 06/2010 17Remote graphic display terminal option, ATV61/ATV71 (continued)Powering up the drive for the first timeWhen powering up the drive

Strany 37

18 BBV46385 06/2010Remote graphic display terminal option, ATV61/ATV71 (continued)Subsequent power-upsDisplay after powering up.The [MAIN MENU]follo

Strany 38

BBV46385 06/2010 19Remote display terminal option, ATV12Description of the terminalThis terminal is a local control unit which can be mounted on the

Strany 39

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-w

Strany 40

20 BBV46385 06/2010Structure of the parameter tablesThe parameter tables contained in the descriptions of the various menus are organized as follows

Strany 41 - [MOTOR CONTROL] (drC-) menu

BBV46385 06/2010 21Compatibility of functionsIncompatible functions The following functions will be inaccessible or deactivated in the cases describ

Strany 42

22 BBV46385 06/2010Compatibility of functionsLogic and analog input application functionsEach of the functions on the following pages can be assigne

Strany 43

BBV46385 06/2010 23List of functions that can be assigned to inputs/outputsLogic inputs Page Code Factory settingNot assigned - - LI5 - LI6Run forwa

Strany 44

24 BBV46385 06/2010List of functions that can be assigned to inputs/outputsAnalog/logic output Page Code Factory settingNot assigned - - AOC/AOVMoto

Strany 45

BBV46385 06/2010 25List of functions that can be assigned to the Network and Modbus control word bitsBits 11 to 15 of the control word Page Code2 pr

Strany 46

26 BBV46385 06/2010ChecklistCarefully read the information contained in the programming, installation and simplified manuals, as well as the informa

Strany 47 - M [2 wire type]

BBV46385 06/2010 27ProgrammingDescription of the HMIFunctions of the display and the keysNormal display, with no fault code displayed and no startup

Strany 48

28 BBV46385 06/2010ProgrammingREMOTE and LOCAL configurationThe LOCAL configuration allows to activate automatically the embedded RUN button and the

Strany 49 - BBV46385 06/2010 49

BBV46385 06/2010 29ProgrammingConfiguring the [Standard mot. freq] (bFr), [2/3 wire control] (tCC), and [Ref.1 channel] (Fr1) parametersThese parame

Strany 50 - [COMMAND] (CtL-) menu

BBV46385 06/2010 1ContentsImportant information _______________________________________________________________________________________ 4Before you

Strany 51

30 BBV46385 06/2010ProgrammingCode Description Adjustment rangeFactory settingtCCM [2/3 wire control][2 wire] (2C)DANGERUNINTENDED EQUIPMENT OPERATI

Strany 52

BBV46385 06/2010 31[SPEED REFERENCE] (rEF-) menuThe [SPEED REFERENCE] (rEF-) menu displays [HMI Frequency ref.] (LFr), [Image input AIV1] (AIV1) or

Strany 53

32 BBV46385 06/2010[SETTINGS] (SEt-) menuThe adjustment parameters can be modified with the drive running or stopped.Note: Changes should preferably

Strany 54

BBV46385 06/2010 33[SETTINGS] (SEt-) menu(1)In corresponds to the nominal drive current indicated in the Installation Manual and on the drive namepl

Strany 55

34 BBV46385 06/2010[SETTINGS] (SEt-) menu(1)In corresponds to the nominal drive current indicated in the Installation Manual and on the drive namepl

Strany 56

BBV46385 06/2010 35[SETTINGS] (SEt-) menu(1)In corresponds to the nominal drive current indicated in the Installation Manual and on the drive namepl

Strany 57

36 BBV46385 06/2010[SETTINGS] (SEt-) menuCode Description Adjustment range Factory settingJPFM [Skip Frequency]0 to 500 Hz 0 HzHelps to prevent prol

Strany 58

BBV46385 06/2010 37[SETTINGS] (SEt-) menuCode Description Adjustment rangeFactory settingSP3M [Preset speed 3]0 to 500 Hz 15 HzgSee page 74.SP4M [Pr

Strany 59

38 BBV46385 06/2010[SETTINGS] (SEt-) menu(1) In corresponds to the nominal drive current indicated in the Installation Manual and on the drive namep

Strany 60

BBV46385 06/2010 39[SETTINGS] (SEt-) menu(1)In corresponds to the nominal drive current indicated in the Installation Manual and on the drive namepl

Strany 61

4 BBV46385 06/2010Important informationNOTICERead these instructions carefully, and look at the equipment to become familiar with the device before

Strany 62 - M [Ramp type]

40 BBV46385 06/2010[SETTINGS] (SEt-) menu(1)Parameter can also be accessed in the [MOTOR CONTROL] (drC-) menu.Code Description Adjustment rangeFacto

Strany 63 - BBV46385 06/2010 63

BBV46385 06/2010 41[MOTOR CONTROL] (drC-) menuWith the exception of [Auto tuning] (tUn), which can power up the motor, parameters can only be change

Strany 64 - [RAMPS] (continued)

42 BBV46385 06/2010[MOTOR CONTROL] (drC-) menu(1)Procedure:- Check that the motor is cold.- Disconnect the cables from the motor terminals.- Measure

Strany 65 - [STOP MODES]

BBV46385 06/2010 43[MOTOR CONTROL] (drC-) menuCode Description Adjustment rangeFactory settingtUnM [Auto tuning][No] (nO)DANGERHAZARD OF ELECTRIC SH

Strany 66 - [STOP MODES](continued)

44 BBV46385 06/2010[MOTOR CONTROL] (drC-) menu(1)Parameter can also be accessed in the [SETTINGS] (SEt-) menu.Code Description Adjustment rangeFacto

Strany 67 - [STOP MODES] (continued)

BBV46385 06/2010 45[MOTOR CONTROL] (drC-) menu(1)[Saving config.] (SCS), [Macro configuration] (CFG), and [Restore config.] (FCS) can be accessed fr

Strany 68

46 BBV46385 06/2010[MOTOR CONTROL] (drC-) menu(1)[Saving config.] (SCS), [Macro configuration] (CFG), and [Restore config.] (FCS) can be accessed fr

Strany 69 - RISK OF DAMAGE TO MOTOR

BBV46385 06/2010 47[INPUTS / OUTPUTS CFG] (I-O-) menuThe parameters can only be modified when the drive is stopped and no run command is present.On

Strany 70 - M [Auto DC inj. level 2]

48 BBV46385 06/2010[INPUTS / OUTPUTS CFG] (I-O-) menuCode Description Adjustment rangeFactory settingrrSM [Reverse assign.][LI2] (LI2)nOLI1LI2LI3LI4

Strany 71 - [SUMMING INPUTS]

BBV46385 06/2010 49[INPUTS / OUTPUTS CFG] (I-O-) menu(1)[Saving config.] (SCS), [Macro configuration] (CFG), and [Restore config.] (FCS) can be acce

Strany 72 - Preset speeds

BBV46385 06/2010 5Before you beginRead and understand these instructions before performing any procedure with this drive.DANGERHAZARD OF ELECTRIC SH

Strany 73 - [PRESET SPEEDS]

50 BBV46385 06/2010[COMMAND] (CtL-) menuThe parameters can only be modified when the drive is stopped and no run command is present.On the optional

Strany 74

BBV46385 06/2010 51[COMMAND] (CtL-) menuThese channels can be combined in order of priority if [ACCESS LEVEL] (LAC) = [Level 1] (L1) or [Level 2] (L

Strany 75 - BBV46385 06/2010 75

52 BBV46385 06/2010[COMMAND] (CtL-) menuSeparate control and reference ([Profile] (CHCF) parameter = [Separate] (SEP)): ReferenceThe [Ref. 2 switchi

Strany 76

BBV46385 06/2010 53[COMMAND] (CtL-) menuReference channel for [ACCESS LEVEL] (LAC) = [Level 1] (L1) or [Level 2] (L2) rEF-SEt-drC-I-0-

Strany 77 - +/- speed

54 BBV46385 06/2010[COMMAND] (CtL-) menuControl channel for [ACCESS LEVEL] (LAC) = [Level 1] (L1) or [Level 2] (L2)The [Forced local assign.] (FLO)

Strany 78 - [+/- SPEED]

BBV46385 06/2010 55[COMMAND] (CtL-) menuReference channel for [ACCESS LEVEL] (LAC) = [Level 3] (L3) rEF-SEt-drC-I-0-CtL-FUn-FLt-COM-SUP-+speed-spee

Strany 79 - PI regulator

56 BBV46385 06/2010[COMMAND] (CtL-) menuControl channel for [ACCESS LEVEL] (LAC) = [Level 3] (L3)Combined reference and controlThe [Ref.1 channel] (

Strany 80 - Setting up the PI regulator

BBV46385 06/2010 57[COMMAND] (CtL-) menuControl channel for [ACCESS LEVEL] (LAC) = [Level 3] (L3)Mixed mode (separate reference and control)The [For

Strany 81 - BBV46385 06/2010 81

58 BBV46385 06/2010[COMMAND] (CtL-) menuNote: There may be an incompatibility between functions (see the incompatibility table, page 21). In this ca

Strany 82

BBV46385 06/2010 59[COMMAND] (CtL-) menuCode Description Adjustment rangeFactory settingrFCM [Ref. 2 switching][ch1 active] (Fr1)Fr1Fr2LI1LI2LI3LI4L

Strany 83 - M [Internal PID ref.]

6 BBV46385 06/2010Before you begina) For additional information, refer to NEMA ICS 1.1 (latest edition), "Safety Guidelines for the Application

Strany 84 - Brake control

60 BBV46385 06/2010[COMMAND] (CtL-) menuCode Description Adjustment range Factory settingCd2M [Cmd channel 2][Modbus] (Mdb)gtErLOCLCCNdbnEtParameter

Strany 85 - BBV46385 06/2010 85

BBV46385 06/2010 61[COMMAND] (CtL-) menu(1)[Saving config.] (SCS), [Macro configuration] (CFG), and [Restore config.] (FCS) can be accessed from sev

Strany 86 - [CURRENT LIMITATION 2]

62 BBV46385 06/2010[APPLICATION FUNCT.] (FUn-) menu The parameters can only be modified when the drive is stopped and no run command is present.On t

Strany 87 - [SWITCHING MOTOR]

BBV46385 06/2010 63[APPLICATION FUNCT.] (FUn-) menu(1)When values higher than 9,999 are displayed on the drive or on the remote display terminal, a

Strany 88

64 BBV46385 06/2010[APPLICATION FUNCT.] (FUn-) menu(1)Parameter can also be accessed in the [SETTINGS] (SEt-) menu.Code Name/Description Adjustment

Strany 89 - [LIMIT SWITCHES]

BBV46385 06/2010 65[APPLICATION FUNCT.] (FUn-) menuCode Name/Description Adjustment range Factory settingStC-b [STOP MODES]SttM [Type of stop][Ramp

Strany 90

66 BBV46385 06/2010[APPLICATION FUNCT.] (FUn-) menuCode Name/Description Adjustment rangeFactory settingStC-b [STOP MODES](continued)SttM [Type of s

Strany 91 - M [Automatic restart]

BBV46385 06/2010 67[APPLICATION FUNCT.] (FUn-) menu(1)Parameter can also be accessed in the [SETTINGS] (SEt-) menu.(2)In corresponds to the nominal

Strany 92

68 BBV46385 06/2010[APPLICATION FUNCT.] (FUn-) menu(1)Parameter can also be accessed in the [SETTINGS] (SEt-) menu.(2)In corresponds to the nominal

Strany 93 - BBV46385 06/2010 93

BBV46385 06/2010 69[APPLICATION FUNCT.] (FUn-) menu(1)Parameter can also be accessed in the [SETTINGS] (SEt-) menu.(2)In corresponds to the nominal

Strany 94 - RISK OF DAMAGE TO THE MOTOR

BBV46385 06/2010 7Documentation structureThe following Altivar 312 technical documents are available on the Schneider Electric website (www.schneide

Strany 95 - LOSS OF CONTROL

70 BBV46385 06/2010[APPLICATION FUNCT.] (FUn-) menu(1)Parameter can also be accessed in the [SETTINGS] (SEt-) menu.(2)In corresponds to the nominal

Strany 96 - RISK OF DAMAGE TO DRIVE

BBV46385 06/2010 71[APPLICATION FUNCT.] (FUn-) menuSumming inputsSee the complete block diagrams on pages 53 and 55.Code Name/Description Adjustment

Strany 97 - BBV46385 06/2010 97

72 BBV46385 06/2010[APPLICATION FUNCT.] (FUn-) menuPreset speeds2, 4, 8 or 16 speeds can be preset, requiring 1, 2, 3 or 4 logic inputs respectively

Strany 98 - [COMMUNICATION] (COM-) menu

BBV46385 06/2010 73[APPLICATION FUNCT.] (FUn-) menuCode Name/Description Adjustment rangeFactory settingPSS-b [PRESET SPEEDS]Note: The "Preset

Strany 99

74 BBV46385 06/2010[APPLICATION FUNCT.] (FUn-) menu(1)Parameter can also be accessed in the [SETTINGS] (SEt-) menu. This parameter will depend on h

Strany 100 - [MONITORING] (SUP-) menu

BBV46385 06/2010 75[APPLICATION FUNCT.] (FUn-) menu(1)Parameter can also be accessed in the [SETTINGS] (SEt-) menu. This parameter will depend on h

Strany 101

76 BBV46385 06/2010[APPLICATION FUNCT.] (FUn-) menu(1)Parameter can also be accessed in the [SETTINGS] (SEt-) menu.Code Name/Description Adjustment

Strany 102

BBV46385 06/2010 77[APPLICATION FUNCT.] (FUn-) menu+/- speedFunction can only be accessed if [ACCESS LEVEL] (LAC) = [Level 2] (L2) or [Level 3] (L3)

Strany 103

78 BBV46385 06/2010[APPLICATION FUNCT.] (FUn-) menuCode Name/Description Adjustment rangeFactory settingUPd-b [+/- SPEED](motorized jog dial)Functio

Strany 104

BBV46385 06/2010 79[APPLICATION FUNCT.] (FUn-) menuPI regulatorBlock diagramThe function is activated by assigning an analog input to the PI feedbac

Strany 105 - Migration ATV31 - ATV312

8 BBV46385 06/2010Software enhancementsSince it was first marketed, the Altivar ATV 312 has been equipped with additional functions. Software versio

Strany 106 - 106 BBV46385 06/2010

80 BBV46385 06/2010[APPLICATION FUNCT.] (FUn-) menu"Manual - Automatic" operation with PIThis function combines the PI regulator and [Ref.

Strany 107 - (continued)

BBV46385 06/2010 81[APPLICATION FUNCT.] (FUn-) menu(1)Parameter(s) can also be accessed in the [SETTINGS] (SEt-) menu.Code Name/Description Adjustme

Strany 108 - 108 BBV46385 06/2010

82 BBV46385 06/2010[APPLICATION FUNCT.] (FUn-) menu(1)Parameter(s) can also be accessed in the [SETTINGS] (SEt-) menu.Code Name/Description Adjustme

Strany 109 - BBV46385 06/2010 109

BBV46385 06/2010 83[APPLICATION FUNCT.] (FUn-) menu(1)Parameter(s) can also be accessed in the [SETTINGS] (SEt-) menu.Code Name/Description Adjustme

Strany 110 - : Initialization in

84 BBV46385 06/2010[APPLICATION FUNCT.] (FUn-) menuBrake controlFunction can only be accessed if [ACCESS LEVEL] (LAC) = [Level 2] (L2) or [Level 3]

Strany 111 - Index of functions

BBV46385 06/2010 85[APPLICATION FUNCT.] (FUn-) menu(1)In corresponds to the nominal drive current indicated in the Installation Manual and on the dr

Strany 112 - 112 BBV46385 06/2010

86 BBV46385 06/2010[APPLICATION FUNCT.] (FUn-) menu(1)Parameter can also be accessed in the [SETTINGS] (SEt-) menu.(2)In corresponds to the nominal

Strany 113 - BBV46385 06/2010 113

BBV46385 06/2010 87[APPLICATION FUNCT.] (FUn-) menuCode Name/Description Adjustment rangeFactory settingCHP-b [SWITCHING MOTOR]Function can only be

Strany 114 - 114 BBV46385 06/2010

88 BBV46385 06/2010[APPLICATION FUNCT.] (FUn-) menu(1)Parameter can also be accessed in the [SETTINGS] (SEt-) menu.(2)In corresponds to the nominal

Strany 115 - BBV46385 06/2010 115

BBV46385 06/2010 89[APPLICATION FUNCT.] (FUn-) menuManagement of limit switchesFunction can only be accessed if [ACCESS LEVEL] (LAC) = [Level 2] (L2

Strany 116 - BBV46385 06/2010

BBV46385 06/2010 9Steps for setting up the drive3. Configure:v The nominal frequency of the motor[Standard mot. freq] (bFr) page 41 if this isnot 50

Strany 117 - BBV46385 06/2010 117

90 BBV46385 06/2010[APPLICATION FUNCT.] (FUn-) menu(1) [Saving config.] (SCS), [Macro configuration] (CFG), and [Restore config.] (FCS) can be acces

Strany 118 - 118 BBV46385 06/2010

BBV46385 06/2010 91[FAULT MANAGEMENT] (FLt-) menuThe parameters can only be modified when the drive is stopped and no run command is present.On the

Strany 119 - BBV46385 06/2010 119

92 BBV46385 06/2010[FAULT MANAGEMENT] (FLt-) menuCode Description Adjustment rangeFactory settingtArM [Max. restart time][5 min] (5)g510301h2h3hCtPa

Strany 120 - 120 BBV46385 06/2010

BBV46385 06/2010 93[FAULT MANAGEMENT] (FLt-) menuCode Description Adjustment rangeFactory settingFLrM [Catch on the fly][No] (nO)nOYESUsed to enable

Strany 121 - BBV46385 06/2010 121

94 BBV46385 06/2010[FAULT MANAGEMENT] (FLt-) menuCode Description Adjustment rangeFactory settingOPLM [Output Phase Loss][Yes] (YES)DANGERHAZARD OF

Strany 122 - 122 BBV46385 06/2010

BBV46385 06/2010 95[FAULT MANAGEMENT] (FLt-) menuCode Description Adjustment rangeFactory settingSLLM [Modbus fault mgt][Fast stop] (FSt)WARNINGLOSS

Strany 123 - BBV46385 06/2010 123

96 BBV46385 06/2010[FAULT MANAGEMENT] (FLt-) menuCode Description Adjustment rangeFactory settingdrnM [Derated operation][No] (nO)nOYESLowers the tr

Strany 124 - 124 BBV46385 06/2010

BBV46385 06/2010 97[FAULT MANAGEMENT] (FLt-) menuCode Description Adjustment rangeFactory settingrPrM [Operating t. reset][No] (nO)nOrtHv [No] (nO):

Strany 125 - BBV46385 06/2010 125

98 BBV46385 06/2010[COMMUNICATION] (COM-) menuThe parameters can only be modified when the drive is stopped and no run command is present. Modificat

Strany 126

BBV46385 06/2010 99[COMMUNICATION] (COM-) menuCode Description Adjustment rangeFactory settingFLOM [Forced local assign.][No] (nO)nOLI1LI2LI3LI4LI5L