Shrnutí obsahu

Strany 1 - Installation Guide

31002947 00Advantys STB System Planning and Installation Guide890USE17100 Version 1.031002947 00

Strany 2

Site Requirements10890USE17100 September 2003Advantys STB Islands of AutomationSystem DefinitionAdvantys STB is an open, modular distributed I/O syste

Strany 3 - Table of Contents

Commissioning100890USE17100 September 2003

Strany 4 - 4 890USE17100 September 2003

890USE17100 September 2003 101Glossary10Base-T An adaptation of the IEEE 802.3 (Ethernet) standard, the 10Base-T standard uses twisted-pair wiring wit

Strany 5 - Safety Information

Glossary102890USE17100 September 2003ARP address resolution protocol. IP’s network layer protocol uses ARP to map an IP address to a MAC (hardware) ad

Strany 6

Glossary890USE17100 September 2003 103CiA CAN in Automation. CiA is a non-profit group of manufacturers and users dedicated to developing and supporti

Strany 7 - About the Book

Glossary104890USE17100 September 2003EDS electronic data sheet. The EDS is a standardized ASCII file that contains information about a network device’

Strany 8

Glossary890USE17100 September 2003 105Fipio Fieldbus Interface Protocol (FIP). An open fieldbus standard and protocol that conforms to the FIP/World F

Strany 9 - Site Requirements for an

Glossary106890USE17100 September 2003HMI human-machine interface An operator interface, usually graphical, for industrial equipment.HMI human-machine

Strany 10 - Site Requirements

Glossary890USE17100 September 2003 107IEC type 1+ input Type 1+ digital inputs support sensor signals from mechanical switching devices such as relay

Strany 11

Glossary108890USE17100 September 2003LAN local area network. A short-distance data communications network.light industrial I/OAn Advantys STB I/O modu

Strany 12 - 1 2 4 653

Glossary890USE17100 September 2003 109N.C. contact normally closed contact. A relay contact pair that is closed when the relay coil is de-energized an

Strany 13 - Inside the Enclosure

Site Requirements890USE17100 September 2003 11Mechatronics One of the key reasons for selecting Advantys STB is so that you can design a system where

Strany 14 - Power Supply Selection

Glossary110890USE17100 September 2003output polarity An output channel’s polarity determines when the output module turns its field actuator on and wh

Strany 15 - Sensor bus

Glossary890USE17100 September 2003 111preferred module An I/O module that functions as an auto-addressable node on an Advantys STB island but is not i

Strany 16

Glossary112890USE17100 September 2003repeater An interconnection device that extends the permissible length of a bus.reverse polarity protectionUse of

Strany 17 - Extending the Island

Glossary890USE17100 September 2003 113SELV safety extra low voltage. A secondary circuit designed and protected so that the voltage between any two ac

Strany 18

Glossary114890USE17100 September 2003standard network interfaceAn Advantys STB network interface module designed at moderate cost to support the kind

Strany 19 - 890USE17100 September 2003 19

Glossary890USE17100 September 2003 115UDP user datagram protocol. A connectionless mode protocol in which messages are delivered in a datagram to a de

Strany 20

Glossary116890USE17100 September 2003

Strany 21 - 890USE17100 September 2003 21

CBA890USE17100 September 2003 117AAdvantys configuration software, 96Advantys STB modulesinserting and removing from bases, 88installing, 58agency app

Strany 22 - Ω temination resistor switch

Index118890USE17100 September 2003IInsertion/removal cyclesAdvantys STB modules and bases, 88Island busLEDs, 98operational mode, 98island busmastery o

Strany 23 - Operating Environment

Index890USE17100 September 2003 119TTest mode, 98Testingyour application with live inputs, 71Troubleshooting, 95using the Advantys STB LEDs, 98

Strany 24

Site Requirements12890USE17100 September 2003An Illustrative ExampleThe illustration below shows an example of a primary segment with I/O modules from

Strany 25 - 890USE17100 September 2003 25

Index120890USE17100 September 2003

Strany 26

Site Requirements890USE17100 September 2003 13Inside the EnclosureOpen System RequirementTo assure performance to specs, open equipment must be instal

Strany 27 - Procedures

Site Requirements14890USE17100 September 2003Power Supply SelectionOverview In an Advantys island there are at least three connections that need to be

Strany 28 - Installation

Site Requirements890USE17100 September 2003 15Sensor and Actuator PowerThe power distribution module (PDM) distributes field power across the island’s

Strany 29

Site Requirements16890USE17100 September 2003Wattage RequirementsThe NIM must be supplied 13 W of power. In addition each BOS module on your island mu

Strany 30

Site Requirements890USE17100 September 2003 17Extending the IslandSummary Advantys STB allows you to extend the island bus out to multiple segments of

Strany 31

Site Requirements18890USE17100 September 2003Advantys STB Bus Extension CablesAdvantys STB bus extension cables are specially designed cables in the I

Strany 32

Site Requirements890USE17100 September 2003 19I/O Modules in a SegmentThe primary segment is where the NIM resides. It supports as many I/Os whose tot

Strany 33 - Schneider catalog

2890USE17100 September 2003

Strany 34 - The DIN Rail

Site Requirements20890USE17100 September 2003Preferred ModulesAn island bus can support auto-addressable preferred modules as well as Advantys STB I/O

Strany 35

Site Requirements890USE17100 September 2003 21A preferred module can also pass the island bus communications signal to an extension segment of Advanty

Strany 36

Site Requirements22890USE17100 September 2003Standard CANopen DevicesAn island bus can support standard CANopen devices as well as Advantys STB I/O mo

Strany 37 - How to Install the

Site Requirements890USE17100 September 2003 23Operating EnvironmentTypes of Environmental SpecificationsThe following information describes systemwide

Strany 38

Site Requirements24890USE17100 September 2003Environmental RequirementsThis equipment meets agency certification for UL, CSA, CE and FM class 1 div 2.

Strany 39 - Step Action

Site Requirements890USE17100 September 2003 25Electromagnetic SusceptibilityThe following table lists the electromagnetic susceptibility specification

Strany 40 - NIM from the DIN

Site Requirements26890USE17100 September 2003

Strany 41 - 890USE17100 September 2003 41

890USE17100 September 2003 272Advantys STB System Installation ProceduresAt a GlanceOverview This chapter focuses on procedures for constructing the b

Strany 42 - Keying Considerations

Installation28890USE17100 September 2003The Layout of Modules on an Island BusMaking a Plan Before you begin to install the modules, you need to estab

Strany 43

Installation890USE17100 September 2003 29Positioning the STB I/OThe Advantys STB I/O modules need to be installed in structures called segments. A seg

Strany 44

890USE17100 September 2003 3Table of ContentsSafety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5About the Bo

Strany 45 - 890USE17100 September 2003 45

Installation30890USE17100 September 2003Suggested Design ExampleThe following illustration shows a typical island system with one segment (the primary

Strany 46 - Key slots

Installation890USE17100 September 2003 31Determining Power Distribution RequirementsThe island bus is designed to distribute field power to all its I/

Strany 47 - 890USE17100 September 2003 47

Installation32890USE17100 September 2003The illustration above shows an island segment mounted on a DIN rail. The segment comprises:a NIM in the leftm

Strany 48

Installation890USE17100 September 2003 33Cable Channels Cable channels are recommended for an island’s physical stability and ease of system assembly.

Strany 49 - Connection

Installation34890USE17100 September 2003The DIN RailCarrier Rails for the Island BusThe island is mounted on one or more DIN carrier rails. A DIN rail

Strany 50 - PDM Pinwheels Connectors

Installation890USE17100 September 2003 35Rail Mounting ConsiderationsIf you are using 7.5 mm DIN rail, make sure that the region along the rail where

Strany 51 - 890USE17100 September 2003 51

Installation36890USE17100 September 2003Installing the NIM in the First Location on the IslandThe First Module on the Island BusEvery Advantys STB isl

Strany 52

Installation890USE17100 September 2003 37How to Install the NIMUnlike other Advantys STB modules, the NIM’s mounting base is permanently attached to t

Strany 53 - 890USE17100 September 2003 53

Installation38890USE17100 September 20033 Turn the release screw (2) on the NIM so that the mounting clips on the back are in their relaxed state. 4 A

Strany 54

Installation890USE17100 September 2003 39FE Contacts One of the roles of the DIN rail is to provide a FE for the modules on the island. FE provides th

Strany 55 - 890USE17100 September 2003 55

4 890USE17100 September 2003Chapter 5 Commissioning an Advantys STB Island . . . . . . . . . . . . . . . . 81Overview . . . . . . . . . . . . . . . .

Strany 56 - Primary Segment

Installation40890USE17100 September 2003How to Remove a NIM from the DIN RailIf for any reason you need to remove the NIM from the rail on which it ha

Strany 57 - 890USE17100 September 2003 57

Installation890USE17100 September 2003 413 Use a small flathead screwdriver to turn the release screw 90 degrees in either direction. This will spread

Strany 58

Installation42890USE17100 September 2003Keying ConsiderationsOverview Along with the inherent keying designed into Advantys STB products and the wise

Strany 59 - 890USE17100 September 2003 59

Installation890USE17100 September 2003 43Creating a Keying SchemeThere are a multitude of keying schemes you can use in you Advantys STB island. Here

Strany 60

Installation44890USE17100 September 2003Here are the keying pattern combinations we will use to key our base/module combinations. The first six are un

Strany 61 - Module from its

Installation890USE17100 September 2003 45Referencing the previous pattern table, the following table shows us where to add keys to, or remove break-of

Strany 62

Installation46890USE17100 September 2003How to Key the I/O Module to Base ConnectionTo key an I/O module to base connection, use the STB XMP 7800 keyi

Strany 63 - Island Bus

Installation890USE17100 September 2003 473 Push the key, still attached to the STB XMP 7800 pinwheel into the key slot on the module. Then lift the pi

Strany 64 - Island Bus Extensions

Installation48890USE17100 September 2003How to Key the I/O Module Field Wire ConnectionUse an STB XMP 7800 keying kit to key an I/O module field wi

Strany 65 - 890USE17100 September 2003 65

Installation890USE17100 September 2003 49How to Key the NIM Power ConnectionThe NIM power connector is a two-pin version of the I/O connector. Follow

Strany 66 - Extending the Island Bus

890USE17100 September 2003 5§Safety InformationImportant InformationNOTICE Read these instructions carefully, and look at the equipment to become fami

Strany 67 - 890USE17100 September 2003 67

Installation50890USE17100 September 2003Keying the PDM Power ConnectionKeying the scalloped power connection on the front of a PDM requires keying pin

Strany 68

Installation890USE17100 September 2003 512 Push the key, still attached to the STB XMP 7800 pinwheel all the way into the key slot on the connector pl

Strany 69 - Considerations

Installation52890USE17100 September 2003Interlocking Base Units on the DIN RailThe Backplane of the Island BusAfter the NIM has been attached to the D

Strany 70

Installation890USE17100 September 2003 53The Base Units The following table lists the six types of bases. Five of these base types may be used in the

Strany 71 - Safety Switching

Installation54890USE17100 September 20034 Align the electrodes on the base with the electrode channels on the NIM and push the base toward the DIN rai

Strany 72

Installation890USE17100 September 2003 55Installing the Last Device on the Primary SegmentOne or More Segments?The last device on the island bus needs

Strany 73 - 890USE17100 September 2003 73

Installation56890USE17100 September 2003How to Terminate the Primary SegmentUse the following procedure when you terminate the island bus at the end o

Strany 74 - EMC Kits

Installation890USE17100 September 2003 57How to Remove a Termination PlateUse the following procedure to remove a termination plate at the end of prim

Strany 75 - FE grounding clamp

Installation58890USE17100 September 2003Installing Advantys STB Modules in their BasesSummary The insertion of an Advantys STB module into its base is

Strany 76 - Assembly

Installation890USE17100 September 2003 59How to Insert a Module in a BaseDo the following:Step Action1 Guide the bottom of the module into the tray at

Strany 77 - 890USE17100 September 2003 77

Safety Information6890USE17100 September 2003PLEASE NOTE Electrical equipment should be serviced only by qualified personnel. No responsi-bility is as

Strany 78

Installation60890USE17100 September 20034 Apply pressure to the bottom latches (items 2 and 4 above) until you hear them click together. Note Make sur

Strany 79 - 890USE17100 September 2003 79

Installation890USE17100 September 2003 61How to Remove a Module from its BaseTo remove an I/O module from its base:Step Action1 Remove any connectors

Strany 80

Installation62890USE17100 September 2003

Strany 81 - Overview

890USE17100 September 2003 633Extending an Advantys STB Island BusOverviewWhy Extend the Island Bus?There are five key reasons why you might want to e

Strany 82

Extending the Island Bus64890USE17100 September 2003Island Bus ExtensionsBus Extensions An island bus can be extended beyond the primary segment by us

Strany 83 - 890USE17100 September 2003 83

Extending the Island Bus890USE17100 September 2003 65Advantys STB Bus Extension CablesAdvantys STB bus extension cables are specially designed cables

Strany 84

Extending the Island Bus66890USE17100 September 2003Preferred ModulesPreferred modules must also be equipped with input and output IEEE 1394-style con

Strany 85 - Configuring the Island

Extending the Island Bus890USE17100 September 2003 67Installing Extension Segments of Advantys STB Island ModulesPreliminary ConsiderationsAn island b

Strany 86

Extending the Island Bus68890USE17100 September 2003Installing a Preferred Module ExtensionPreliminary ConsiderationsWhen you use preferred modules on

Strany 87

890USE17100 September 2003 694Safety and Grounding ConsiderationsOverviewSummary Some required and optional precautions for making Advantys STB island

Strany 88

890USE17100 September 2003 7About the BookAt a GlanceDocument Scope This book describes concepts for planning and procedures for installing an Advanty

Strany 89 - 890USE17100 September 2003 89

Safety70890USE17100 September 2003Power Isolation Requirements on the Island BusIsolation RequirementsThe power source for the NIM, and any BOS module

Strany 90

Safety890USE17100 September 2003 71Safety SwitchingAdvantage of the Power Distribution MethodOne of the key features of Advantys STB island is the sep

Strany 91 - 890USE17100 September 2003 91

Safety72890USE17100 September 2003The Protective Earth ConnectionPE Contact for the IslandOne of the key functions of a PDM, in addition to distributi

Strany 92

Safety890USE17100 September 2003 73The Functional Earth ConnectionFunctional Earth (FE) on the DIN RailThe DIN rail for your Advantys STB island is co

Strany 93 - 890USE17100 September 2003 93

Safety74890USE17100 September 2003EMC KitsOverview EMC kits reduce electromagnetic and radio interference by grounding, at close proximity, the shiel

Strany 94

Safety890USE17100 September 2003 75The Kits There are three kits you can use to ground your shielded cable. To do an initial set up you need STB XSP 3

Strany 95

Safety76890USE17100 September 2003STB XSP 3000 AssemblyUse the following procedure to assemble kit STB XSP 3000. After this is done go to the next ass

Strany 96

Safety890USE17100 September 2003 774 Push the side brackets toward both ends of your segment so that they are snug against its walls, and tighten the

Strany 97

Safety78890USE17100 September 20036 With the grounding bar cut to length, slide the FE grounding clamp onto the grounding bar and tighten the lock dow

Strany 98

Safety890USE17100 September 2003 79Clamp and Cable AssemblyThe grounding clamps are used to ground the shielding of the stripped cable to the FE groun

Strany 99 - 890USE17100 September 2003 99

About the Book8890USE17100 September 2003Product Related WarningsSchneider Electric assumes no responsibility for any errors that may appear in this d

Strany 100 - Commissioning

Safety80890USE17100 September 20032 Strip 2.5 cm of insulation off of your cable to expose the braided shield below. (Be sure the cable on either side

Strany 101 - Glossary

890USE17100 September 2003 815Commissioning an Advantys STB IslandOverviewCommissioning the IslandOnce the island hardware has been installed and you

Strany 102

Commissioning82890USE17100 September 2003Making Fieldbus and Power ConnectionsOverview The fieldbus and power connections to your island must be made

Strany 103

Commissioning890USE17100 September 2003 83Power ConnectionsThere are at least three power connections to be made to your island from your source power

Strany 104

Commissioning84890USE17100 September 2003Here is a 24 V parallel power scheme for an Advantys STB island. 123456PowerSupply

Strany 105

Commissioning890USE17100 September 2003 85Configuring the IslandSummary There are three ways to configure your Advantys STB I/O:Using the I/O default

Strany 106

Commissioning86890USE17100 September 2003Custom ConfigurationCustom I/O configuration using the Advantys configuration software is done after your isl

Strany 107

Commissioning890USE17100 September 2003 87Removable Memory CardThe optional removable memory card (I2C SIM card, part STB XMP 4400) lets you store, re

Strany 108

Commissioning88890USE17100 September 2003Hot Swapping Advantys STB ModulesModule Insertion and RemovalThe assembled base units on a DIN rail together

Strany 109

Commissioning890USE17100 September 2003 89Definition Hot swapping is the ability to replace an I/O module in a base unit while the island is under pow

Strany 110

890USE17100 September 2003 91Site Requirements for an Advantys STB Island Installation At a GlanceOverview This chapter describes the external require

Strany 111

Commissioning90890USE17100 September 2003Hot Swapping Modules with the Same Model NumberIf an I/O module is removed from its base and then replaced by

Strany 112

Commissioning890USE17100 September 2003 91Do Not Hot Swap Modules with Different Model NumbersIf an I/O module is removed from its base and then repla

Strany 113

Commissioning92890USE17100 September 2003Mandatory Module ConsiderationsIf the island contains any I/O modules that have been configured as mandatory,

Strany 114

Commissioning890USE17100 September 2003 93If we remove an optional module that resides to the right of any and all mandatory modules, as shown below,

Strany 115

Commissioning94890USE17100 September 2003Suppose that the module in location 4 is mandatory and the optional module in location 2 is removed from its

Strany 116

Commissioning890USE17100 September 2003 95Fault Detection and TroubleshootingSummary By connecting to your islands NIM via its CFG port and by viewing

Strany 117

Commissioning96890USE17100 September 2003Port Parameters The CFG port supports the following communication parameters:Connections An STB XCA 4002 prog

Strany 118 - 890USE17100 September 2003

Commissioning890USE17100 September 2003 97Description The illustration shows a typical LED array: Use the condition table below to look up what your L

Strany 119 - Troubleshooting, 95

Commissioning98890USE17100 September 2003LED Condition TableThe table that follows describes the island bus condition(s) communicated by the LEDs, and

Strany 120

Commissioning890USE17100 September 2003 99off blink: 2 off Assignment error—the NIM has detected a module assignment error; the island bus is not star