15. Signal inputs
15.1 Connecting the inputs to the control panel
The FX-MC2 board has two clean contact input connectors.
Each FX-IOC board has four clean contact input connectors.
Fault in fire alarm router equipment
Normally open / monitored
Normally open / closed
Monitored / not monitored
Fault in fault warning router equipment
Normally open / monitored
Normally open / closed
Monitored / not monitored
- +IN2 - +IN1
4k7
1k54
Normally open / monitored
Normally closed / not monitored
- +IN2 - +IN1
4k7
1k54
Normally closed / monitored
Normally open / not monitored
IN 1
IN 2
IN 3
IN 4
IN 4
+ -
IN 3
+ -
IN 2
+ -
IN 1
+ -
1. Disconnect all power from the control panel.
2. Select suitable inputs and connect the device to be monitored (e.g. extinguisher call point, router fault
output) to the control panel.
3. Start the control panel.
4. If the control panel gives an earth leak indication, press the “BUZZER SILENCE”- button and disconnect
all power. Repair any fault and restart the control panel.
5. Test the operation of the inputs with the connected device (remember that a fire alarm or fault warning
also activates fire and fault alarm devices and alarm routing equipment).
15.2 Testing the inputs
The inputs for Fault in fire alarm router, Fault in fault warning router and Fault in extinguisher can be tested without
activation of fault warning outputs, as follows:
Press the wheel to activate the menu and select:
Then press again the wheel and select:
MC MONITORED INPUT 1 or 2
Press the “TEST”- button, at which the display will show the text:
The display indicates now the status of the input.
The test is stopped by pressing the “TEST”- button.