10
Hardware setup
Description of terminals
Terminal Function
24V Power supply for the "Controller Inside" card, logic outputs and analog outputs.
If allowed by the power consumption table (for example if outputs are not being used), the "Controller Inside" card can
be powered by the 24 V
c power supply in the drive.
If you are using an external power supply:
The "Controller Inside" card should preferably be turned on before the drive. However, the "Controller Inside" card
must without fail be turned on no more than 2s after the drive is turned on.
Failure to follow this instruction locks the drive in card fault mode (ILF). This fault cannot be reset, and the only way to
acknowledge it is to turn off the drive.
Catalog number for a Telemecanique power supply (24 V
c, 2A): ABL7 RE 24 02.
COM Common ground and electrical 0V of the "Controller Inside" card power supply, logic inputs, (LI
pp), outputs (LOpp),
analog inputs (AI
pp) and analog outputs (AOpp).
This ground and electrical 0V are common with the drive ground and electrical 0V. There is therefore no point in
connecting this terminal to the 0V terminal on the drive control terminals.
LI51 to LI60 24 V
c logic inputs
Inputs LI51, LI52, LI59 and LI60 can be configured for the use of 2 counter inputs or 2 incremental encoder inputs:
Counter 1 input: LI51
Incremental encoder 1 inputs: channel A = LI51, channel B = LI52
Counter 2 input: LI59
Incremental encoder 2 inputs: channel A = LI59, channel B = LI60
LO51 to LO56 24 V
c logic outputs
AI51 and AI52 0 ... 20mA analog inputs
AO51 and AO52 0 ... 20mA analog outputs
LI54
LI55
24V
COM
LI51
LI52
LI53
LI60
LI59
LI58
LI57
LI56
LO51
LO56
LO55
LO54
LO53
LO52
AI51
AO52
COM
A051
AI52
COM