Planning Instruction 66571758GB0 Fire Detection 31
8.2 Cables of conventional detection circuits CLC, alarm device lines, input/output lines
FX_
8
10
11
9
No Cable connection
Conductors x
area
Max. length Comments
8
Conventional
detection circuits of
a CLC board
2 x 0.5 mm
2
+
shield
2 x 1.0 mm
2
+
shield
1200 m
(100 )
2400 m
(100 )
The cable resistance of the loop is max. 50 ,
if an Exi barrier is connected to the loop,
otherwise max 100 .
The max. allowed capacitance of the cable is
0.5 µF.
9
FX alarm device
lines
- fire bell, siren line
- fault buzzer line
2 x 0.5 mm
2
or
2 x 1.0 mm
2
or
2 x 2.5 mm
2
To be
calculated
separately
Max. allowed voltage drop defines cable to
be used.
10
FX clean contact
input lines
2 x 0.5 mm
2
2000 m
11
FX clean contact
output lines
2 x 0.5 mm
2
or
2 x 1.0 mm
2
To be
calculated
separately
The equipment receiving the contact signal
may have restrictions on cable properties.
Load controlled by the relay output may
restrict allowed resistance and length per
cross section.