Schneider Electric FX 3NET Uživatelská příručka Strana 50

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 64
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 49
Planning Instruction 66571760GB0 Fire Detection 7
Schneider Electric Pelco Finland Oy
Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571760GB0 49 2011
© 2009 Schneider Electric. All rights reserved.
2. Control group examples
Examples
When the input device and the output device are in the same panel
Input device (e.g. detector) Output device (e.g. relay in panel)
Control A Control B Input event Conf. function Control groups Action
<empty> <empty> Fire alarm Fire alarm outp. 'General' Will be activated ('General'
matches all In-Zone settings,
also empty ones)
<empty> <empty> Fire alarm Fire alarm outp. 'Local' Will be activated ('Local'
matches all In-Zone settings,
also empty ones)
17 <empty> Fire alarm Fire alarm outp. 'General' Will be activated
17 <empty> Fire alarm Fire alarm outp. 'Local' Will be activated
17 21 Fire alarm Fire alarm outp. 003; 021 Will be activated (Control B has
a match in the Control groups)
17 21 Fire alarm Fire alarm outp. 003; Will not be activated (Control
groups doesn't match the In-
Zones)
17 21 Fault alarm Fire alarm outp. 'General' Will not be activated (Output
function doesn't correspond to
the input event)
When the input device and the output device are in different panels
(The panel of the input device is visible to the panel of the output device and the split point between
local and shared control groups is set at the default 100 in the panel of the input device)
Input device
(e.g. detector in panel 1)
Output device (e.g. relay in panel 2)
Control A Control B Input event Conf. function Control groups Action
<empty> <empty> Fire alarm Fire alarm outp. 'General' Will be activated ('General'
matches all In-Zone settings,
also empty ones and in any
visible panel)
<empty> <empty> Fire alarm Fire alarm outp. 'Local' Will not be activated ('Local'
matches all In-Zone settings, but
only in the same panel)
17 <empty> Fire alarm Fire alarm outp. 'General' Will be activated
17 21 Fire alarm Fire alarm outp. 'General' Will be activated
17 <empty> Fire alarm Fire alarm outp. 'Local' Will not be activated
17 21 Fire alarm Fire alarm outp. 'Local' Will not be activated
17 21 Fire alarm Fire alarm outp. 003; 021 Will not be activated (Control B
setting of 21 is local to that
panel and does not match the
Control groups setting of 21)
17 122 Fire alarm Fire alarm outp. 122 Will be activated (Control B
setting of 122 is shared and
matches the Control groups
setting of 122)
Zobrazit stránku 49
1 2 ... 45 46 47 48 49 50 51 52 53 54 55 ... 63 64

Komentáře k této Příručce

Žádné komentáře