Wiring
975-0540-01-01 Revision B 2–9
This guide is for use by qualified personnel only.
Wiring
The following sections provide information about wiring.
Connector Locations
Terminal connectors for DC wiring are located inside the wiring compartment.
The labels above the DC wiring terminals identify all the connection points. See
Figure 2-8.
HAZARD OF ELECTRIC SHOCK AND FIRE
• Do not ground either PV conductor outside of the unit.
• Grounded arrays:
Install a fuse in the correct holder: (+) or (–). Replace the fuse with the
same type and rating (Littelfuse KLKD 1 or equivalent). Fuses must be
replaced by qualified service personnel only.
• Ungrounded (floating) arrays:
Leave both fuse holders empty.
Failure to follow these instructions will result in death or serious injury.
Figure 2-7 Chassis ground connector
Chassis ground
terminals (4)
This symbol identifies the
protective conductor
(grounding) connection.
Ground fault
protection fuse
holders