AS-i Bus
TSXSAZ10 Master PLC Interface
11
03/00
© 2000 Schneider Electric All Rights Reserved
■ Defined as the time between an AS-i input being triggered and an AS-i output (on the same slave) being energized, including the
processing within the PLC program.
Specifications
Type of Module
TSXSAZ10
Product Certifications
AS-i No. 04601, NF C 63-850
AS-i Profile
M2
Ambient Air Temperature
Operation: +32 °F to +140 °F (0 °C to +60 °C), Storage: -13 °F to +158 °F (-25 °C to +70 °C)
Degree of Protection
IP 20
Vibration Resistance
Conforming to IEC 68-2-6, Fc tests.
Shock Resistance
Conforming to IEC 68-2-27, EA tests.
Number of Connectable Slaves
31 AS-i slaves
Number of Inputs/Outputs
124 inputs and 124 outputs
Processing Times ■
Depending on the scan time of the PLC “Master Task”
Execution Time
10 ms 30 ms 60 ms
Average Processing Time
22 ms 50 ms 80 ms
Maximum Processing Time
35 ms 75 ms 135 ms
Bus Connection
By integral terminal within the module (interlock to maintain cable polarity)
Module Power Supply
Supplied directly from the PLC (100–240 Vac, 24 Vdc)
Display Diagnostics
By display panel integrated into the Micro PLC or via a suitable PC terminal using PL7 Micro/Junior
software.
Compliance Standards
UL Listed E194434 CCN NRAQ
CSA Certified LR58905 Class 2252 01