■ The replacement of the back cover of a standard XUJ solid state output detector by this cover enables the detector to be
connected directly to the AS-i bus.
The detectors which may be adapted are: XUJK06353 (reflex system), XUJK063539 (polarized reflex system), XUJK103534
(thru-beam system), XUJK703538 and XUJK123538 (diffuse system with background suppression).
NOTE: The bit D1 is unusable when the XUJZAS1 cover is used on an XUJK703538 or XUJK123538 detector.
▲ With Ø80 mm reflector XUZC80.
● Reference of thru-beam system receiver. The receiver must be used in conjunction with a standard XUJM1000D2 transmitter
(incorporating an M12 connector) with the supply (pins 1 and 3) either being powered from:
- a separate 12 or 24 Vdc supply (current consumption ≤15 mA), or
- the AS-i bus via interface module XZSDA•••••. Supply via an output of an interface module (4 Outputs model XZSDA04D•• or
2 Inputs/2 Outputs model XZSDA22D••, see pages 44 to 47), enables the emitter to be turned on/off for testing purposes.
◆ Indication of weak reception of the transmitted beam, which could be a result of dirty lenses on the detectors, a high degree of
pollution in the atmosphere or disturbance of the optical alignment. Not applicable to diffuse system detectors (see LED function
table, page 25).
Type of Unit
Complete Detectors Back Cover ■
System
Thru-beam 1 Polarized reflex 2 Diffuse with background suppression 1 –
Type of Transmission
Infra-red Red Infra-red –
Nominal Sensing Distance (Sn)
49.2 ft (15 m) 19.7 ft (6 m) ▲ 2.3 ft (0.7 m) 3.94 ft (1.2 m) –
Selection
Catalog Number
XUJK103534AS ● XUJK063539AS XUJK703538AS XUJK123538AS XUJZAS1
Specifications
Product Certifications
AS-i No. 06201
Ambient Air Temperature
Operation: -13 °F to +140 °F (-25 °C to +60 °C). Storage: -40 °F to +176 °F (-40 °C to +80 °C)
Vibration Resistance
7 g (f = 42 to 150 Hz), amplitude ± 1.5 mm (f = 5 to 42 Hz), conforming to IEC 68-2-6
Shock Resistance
30 g, duration 11 ms, conforming to IEC 68-2-27
Degree of Protection
IP 65
Connection
M12 connector
Materials
Case : PEI; window (polarized model) : PMMA PEI
Maximum Switching Frequency
200 Hz –
Delays
First-up: ≤ 15 ms; response: ≤ 2 ms; recovery: ≤ 2 ms –
Power Supply
From the AS-i bus
Indicators
Output: yellow LED. Verification of correct operation: green LED. Alarm: red LED (4)
Current Consumption from Bus
< 70 mA
< 70 mA (with
associated
detector)
Compliance Standards
UL Listed E164353 CCN NKCR
Data Exchange Specifications
AS-i Profile
S1.1
Data Bits (Status)
Bit value 0 1
State D0 (I) No object present Object present
State D1 (I) Alarm “on” ◆ Alarm “off” (4)
State D2 (I) Not used
Data Bits (Commands)
Command D3 (O) Not used
Parameter Bits
Bit value 0 1
Parameter P0 Not used
Parameter P1 Inversion of D0 Non inversion of D0
Parameter P2 Not used
Parameter P3 Not used