AS-i Bus
Power Supply Module and Unit
61
03/00
© 2000 Schneider Electric All Rights Reserved
Specifications
■ The TSXSUPA05 is a constant output maximum power. The power which is not used on one output is available on the other
output. Output currents must respect the above curve.
▲ Constant output maximum power supply unit, see above curve.
Type of Power Supply
Module
TSXSUPA02 TSXSUPA05
Nominal Primary Voltage
100 to 120 Vac 200 to 240 Vac 100 to 120 Vac 200 to 240 Vac
Primary Voltage Range
85 to 132 Vac 170 to 264 Vac 85 to 132 Vac 170 to 264 Vac
Network Limit Frequency
47 to 63 47 to 63 47 to 63 47 to 63
Max. Immunity Time to
Microbreaks
10 ms 10 ms 10 ms 10 ms
Secondary Nominal Voltages
30 V (AS-i bus) 30 V (AS-i bus) 24 V (process)
Voltage Limits
29.5 to 31.6 V 29.5 to 31.6 24 V ± 3%
Output Current
2.4 A at 140 °F (60 °C) (2.8 A peak) See output current curve at 140 °F (60 °C)
Output Power at Secondary
72 W at 140 °F (60 °C) See output current curve at 140 °F (60 °C)
TSXSUPA05
Output Currents ■
Rms Insulation Voltage
Between Primary and
Secondary
3500 Vrms
Withstand to Electric Fields
10 V/m
Safety Extra Low Voltage
(SELV)
Ye s
Interference Withstand Class
FCC class A
Conformity to
Standards
PLC IEC 1131-2
Vibrations IEC 68-2-6-Fc (2 g) IEC 68-2-6-Fc (1 g)
Shocks IEC 68-2-27 (15 g, 11 ms)
Temperature
Storage -13 °F to +158 °F (-25 °C to +70 °C)
Operation +14 °F to +140 °F (-10 °C to +60 °C)
Compliance Standards
UL Listed E194434 CCN NRAQ
CSA Certified LR58905 Class 2252 01
Selection
Description
Current at Secondary Voltages
Catalog Number
30 Vac (AS-i bus) 24 Vdc
Module
100 to 120 Vac and 200 to 240 Vac,
50/60 Hz
2.4 A – TSXSUPA02
Unit
100 to 120 Vac and 200 to 240 Vac,
50/60 Hz
5 A ▲ 7 A ▲ TSXSUPA05
Ground fault detector for AS-i bus – – RM0PAS101
Connection accessories – – See pages 48 and 49.
1
1 2 3 4 5
2
3
4
5
6
7
4.5
5.8
0
3
AS-i Bus Current, A (max)
Auxiliary Supply Current, A (max)