Schneider Electric Splitter Boxes Specifikace Strana 12

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 68
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 11
AS-i Bus
TSXSAY100 Master PLC Interface
© 2000 Schneider Electric All Rights Reserved
12
03/00
PREMIUM AUTOMATION PLATFORM INTERFACE
Introduction
The TSXSAY100 master module for the AS-i bus enables the Premium PLC to act as the AS-i bus
master. In this way, up to 31 sensor/actuator type devices may be managed on one AS-i bus. Up to 4
inputs and/or outputs can be connected to each device, giving a maximum of 248 I/O on one segment.
The AS-i bus consists of a master station (Premium PLC) and slave stations. The TSXSAY100 module,
which supports the AS-i M2 profile, interrogates the devices connected on the AS-i bus and stores the
data (status of sensors/actuators, operational status of devices) in the PLC memory. Communication
management on the AS-i bus is completely transparent with regard to the PLC application program.
An AS-i power supply must be used for powering the various components on the bus. Ideally, this power
supply unit (PSU) should be situated nearest to the components with the largest power demands.
Description
The TSXSAY100 AS-i bus master is a standard format module. It is designed to slide into any position
on the Premium rack except those reserved for the processor and power supply.
The module features, on the front panel:
1. A display unit comprising 4 indicator lamps showing the module operating modes:
RUN: module operating
ERR: module fault
COM: AS-i bus communication active
I/O: AS-i bus I/O fault
2. A display unit comprising 32 indicator lamps for diagnostics of the AS-i bus and of each Slave
connected to the bus.
3. Three indicator lamps specific to the module:
AS-i: AS-i power supply fault
Display Bus: display unit (2) is in Bus display
Display I/O: display unit (2) is in Slave display (state of slave I/O)
4. Two push buttons used for local diagnostics of the AS-i bus.
5. One 3-way male SUB-D connector for connection to the AS-i bus (female connector supplied).
The maximum number of TSXSAY100 modules per PLC station depends on the type of processor
installed. See “Selection” on page 13.
Sensors
AS-i bus
TSXSUPA02
Power Supply
Motor Starter
XBL Keypad
Intelligent Sensors
Premium + TSXSAY100
XVA Indicator Bank
AS-i bus
XAL Control Station
1
2
3
4
5
TSXSAY100
Zobrazit stránku 11
1 2 ... 7 8 9 10 11 12 13 14 15 16 17 ... 67 68

Komentáře k této Příručce

Žádné komentáře