CANopen TeSys U Motor Control Devices
232
31006709 2/2009
The Multifunction Control Unit
The LUCMT1BL Multifunction Control Unit controls, protects and monitors the
LUTM bases (see page 230) and performs the following functions:
Protection
against overcurrent
against thermal overloads, with choice of trip classes from 5 to 30
against ground faults
against phase imbalances
against mechanical jams during or after the start-up phase
against idling
against tripping of the starter via an external signal (as an option)
Warning
The LUCMT Multifunction Control Unit includes a warning associated with each of
the above listed protection functions. The warning level can be configured and is
independent from the protection trip level.
Diagnostic
Records and displays:
number of operating hours for the motor
number of starts
number of trips
cause of each trip
For the last five trips, the multifunction control unit records the status of the motor-
starter at the time of the trip (value of currents, thermal status, and trip type).
When it is used with a short-circuit device and a contactor, as shown above, the
TeSys U C Mu L controller creates a motor starter that provides:
overload protection
motor-starter control
application monitoring
Conditions of Use
Irrespective of the nominal current value of the motor it is supposed to control, the
TeSys U C Mu L controller is always used with an external current transformer
whose:
Secondary is at 1A nominal.
Primary is selected according to the motor’s nominal current.
NOTE: In an installation containing TeSys U starter-controllers and TeSys U
controllers, motor management is identical from the point-of-view of the PLC.