FTB IP67 Devices
31006709 2/2009 85
Advantys FTB 1CN16CM0 Splitter Box Overview
Setting Device Parameters for the Island Bus
The Advantys FTB 1CN16CM0 device, encased in metal, has 3 rotary switches to
define the baud rate and set the node ID of the device on the STB island bus. The
switch set-up procedure is defined in the FTB 1CN-CANOPEN user manual
(W9 1606218 02 11 A01). The following table describes some of the important
steps to help you configure the device as an enhanced CANopen device on an
Advantys STB island.
Step Action Result
1 Turn off the operating voltage.
2 Set the baud rate rotary switch to
position 7.
The baud rate is set to 500 kbaud, which is the
required operating baud rate for an Advantys
STB island when it uses enhanced CANopen
devices.
3 Set the node ID with the other 2
rotary switches.
The maximum allowable node ID setting is 32.
Make sure that the address you set with this
switch matches the address set in the Advantys
configuration software for this device.