Power Meter 750 63230-507-201A1
Section 4—Metering 03/2007
© 2007 Schneider Electric All Rights Reserved16
MODBUS RS485
Pulse Output
Digital Inputs
MIN/MAX VALUES FOR REAL-TIME
READINGS
When certain readings reach their highest or lowest value, the Power Meter
saves the values in its nonvolatile memory. These values are called the
minimum and maximum (min/max) values. The min/max values stored since
the last min/max reset can be viewed using the Power Meter display. See
Table 4– 1 for a list of the minimum and maximum values stored in the
PM750. The min/max value for power is based on the unsigned value of
power.
POWER FACTOR MIN/MAX
CONVENTIONS
The min/max value for power factor is based on the unsigned value of
power factor. See “How Signed Power Factor is Stored in the Register” on
page 48 for more information on power factor.
DEMAND READINGS The power meter provides a variety of demand readings. Table 4– 2 lists the
available demand readings and their reportable ranges.
Local or Remote Setup
Type of distribution system
3-phase 3- or 4-wire with 1, 2, or 3 CTs, two- or
single-phase
Rating of current transformers
Primary 5 to 32,767 A
Secondary 5 or 1 A
Voltage
Primary 3,276,700 V max
Secondary 100, 110, 115, 120
Calculation interval for demand currents 1 to 60 minutes
Calculation interval for demand power 1 to 60 minutes
Table 4– 1: Power Meter Characteristics (continued)
Functions
RS485 link 2-wire
Communication protocol MODBUS RTU
Settings
Communication address 1 to 247
Baud rate (communication speed) 2400, 4800, 9600, 19200 baud
Parity none, even, odd
Pulse Output
Three Modes: External Control, Alarm
Mode, Active Energy Pulse
Solid state relay
Digital Inputs
Two Modes: Normal, Demand Sync 2 digital outputs
Table 4– 2: Demand Readings
Demand Readings Reportable Range
Demand Current, Per-Phase
Last Complete Interval
Peak
0 to 32,767 A
0 to 32,767 A
Demand Real Power, 3Ø Total
Last Complete Interval
Peak
0 to 3276.70 MW
0 to 3276.70 MW