Power Meter 750 63230-507-201A1
Appendix B—Register List 03/2007
© 2007 Schneider Electric All Rights Reserved42
4059
Frequency
Minimum
1 Integer RO Y 0.01 Hz 4500-6500 derived from Phase A
4060
Current, A,
Minimum
1 Integer RO Y I Amp 0-32767
4061
Current, B,
Minimum
1 Integer RO Y I Amp 0-32767
4062
Current, C,
Minimum
1 Integer RO Y I Amp 0-32767
4064
Voltage, A-N,
Minimum
1 Integer RO Y V Volt 0-32767
4065
Voltage, B-N,
Minimum
1 Integer RO Y V Volt 0-32767
4066
Voltage, C-N,
Minimum
1 Integer RO Y V Volt 0-32767
4067
Voltage, A-B,
Minimum
1 Integer RO Y V Volt 0-32767
4068
Voltage, B-C,
Minimum
1 Integer RO Y V Volt 0-32767
4069
Voltage, C-A,
Minimum
1 Integer RO Y V Volt 0-32767
4070
Current, A, THD
Minimum
1 Integer RO Y 0.1 % 0-10000
4071
Current, B, THD
Minimum
1 Integer RO Y 0.1 % 0-10000
4072
Current, C, THD
Minimum
1 Integer RO Y 0.1 % 0-10000
4074
Voltage, A-N, THD
Minimum
1 Integer RO Y 0.1 % 0-10000
4075
Voltage, B-N, THD
Minimum
1 Integer RO Y 0.1 % 0-10000
4076
Voltage, C-N, THD
Minimum
1 Integer RO Y 0.1 % 0-10000
4077
Voltage, A-B, THD
Minimum
1 Integer RO Y 0.1 % 0-10000
4078
Voltage, B-C, THD
Minimum
1 Integer RO Y 0.1 % 0-10000
4079
Voltage, C-A, THD
Minimum
1 Integer RO Y 0.1 % 0-10000
4080
Real Power, Total
Maximum
1 Integer RO Y W kW 0-32767
4081
Apparent Power, Total
Maximum
1 Integer RO Y W kVA 0-32767
4082
Reactive Power, Total
Maximum
1 Integer RO Y W kVAR 0-32767
4083
Power Factor, Total
Maximum
1 Integer RO Y 0.0001 - 0-10000
4084
Frequency
Maximum
1 Integer RO Y 0.01 Hz 4500-6500 derived from Phase A
Table B– 4: Register Listing—Min Max Values (continued)
Min Max values
Reg Name Size Type Access NV Scale Units Range Notes
RO = Read Only
R/W = Read/Write
NV = Nonvolatile.
Komentáře k této Příručce