63230-507-201 Power Meter 750
03/2007 Section 5—Input/Output Capabilities
© 2007 Schneider Electric All Rights Reserved
25
Setting Up the Digital Output
Set Up Output for Pulse
Set Up Output for Alarms
1. In SETUP mode, press
###: until D OUT
is visible.
2. Press D OUT.
3. Select OFF or ON for the desired output
mode by pressing
+. Depending on
which mode is set to ON, the other values
change automatically.
4. Select ON for EXT to choose external
mode. For setting up pulse or alarm
output mode, see below.
5. Press OK when output mode is complete

$/3%450
 /+

/M
@,!2-
05,3%
%W4

1. On the DO SETUP screen, select ON for
PULSE.
2. Select the pulse duration option. Values
available are: 10, 50,100, 300, 500, or
1000 MSEC (milliseconds).
3. Select the pulse weight option. Values
available are: 0.01, 0.1, 1, 10, 100, 1000,
or 10000 for kWH/P.
4. Press OK when output setup is complete
to return to the SETUP MODE screen.

05,3%33%450
 /+
+7(0
-3%#

1. On the DO SETUP screen, select ON for
ALARM.
2. Using the
<-- and --> buttons, scroll
through the alarms until you reach the
alarm(s) you want to set.
3. Press
+ to “mark” the selected alarm(s).
When the alarm is selected, asterisks will
appear on either side of the alarm name.
4. Press
1; return to the DO SETUP
screen.
5. Press OK to return to the SETUP MODE
screen.

NUDQJV




