Power Meter 750 63230-507-201A1
Appendix B—Register List 03/2007
© 2007 Schneider Electric All Rights Reserved46
4156
Alarm Position 2
Configuration
16 - R/CW Y - - - See Alarm Configuration Template
4172
Alarm Position 3
Configuration
16 - R/CW Y - - - See Alarm Configuration Template
4188
Alarm Position 4
Configuration
16 - R/CW Y - - - See Alarm Configuration Template
4204
Alarm Position 5
Configuration
16 - R/CW Y - - - See Alarm Configuration Template
4220
Alarm Position 6
Configuration
16 - R/CW Y - - - See Alarm Configuration Template
4236
Alarm Position 7
Configuration
16 - R/CW Y - - - See Alarm Configuration Template
4252
Alarm Position 8
Configuration
16 - R/CW Y - - - See Alarm Configuration Template
4268
Alarm Position 9
Configuration
16 - R/CW Y - - - See Alarm Configuration Template
4284
Alarm Position 10
Configuration
16 - R/CW Y - - - See Alarm Configuration Template
4300
Alarm Position 11
Configuration
16 - R/CW Y - - - See Alarm Configuration Template
4316
Alarm Position 12
Configuration
16 - R/CW Y - - - See Alarm Configuration Template
4332
Alarm Position 13
Configuration
16 - R/CW Y - - - See Alarm Configuration Template
4348
Alarm Position 14
Configuration
16 - R/CW Y - - - See Alarm Configuration Template
4364
Alarm Position 15
Configuration
16 - R/CW Y - - - See Alarm Configuration Template
Alarm Configuration Template
Reg Name Size Type Access NV Scale Units Range Notes
Base Alarm Type 1 Integer R/CW Y - -
10 = Over
20 = Under
60 = Digital (OFF to ON)
61 = Digital (ON to OFF)
Base + 1 Test Register 1 Integer R/CW Y - -
4006 - 4104,
4110 - 4111,
4115 - 4116
Base + 2 Enable 1 Integer R/CW Y - - 0 - 1
0 = Disable (default)
1 = Enable
Base + 3 Output Association 1 Integer R/CW Y - - 0 - 1
0 = Disable (default)
1 = Enable
Base + 4 Pickup Magnitude 1 Integer R/CW Y 0 - 32767
Will only evaluate based on Register
Value, will not apply scaler
Base + 5 Dropout Magnitude 1 Integer R/CW Y 0 - 32767
Will only evaluate based on Register
Value, will not apply scaler
Table B– 6: Register Listing—Alarm Setup and Status (continued)
Alarm Setup & Status
Reg Name Size Type Access NV Scale Units Range Notes
RO = Read Only
R/W = Read/Write
NV = Nonvolatile.