63230-507-201A1 Power Meter 750
03/2007 Appendix C—Instrument Transformer Wiring: Troubleshooting Guide
© 2007 Schneider Electric All Rights Reserved
55
Table C– 13:Section IV—Case E
Symptoms: 4-Wire Possible Causes
kW = near 0
kVA = near 0
3-phase average power factor flip-flopping lead and lag
Voltages, currents, and kVA are normal
Two CT secondary leads are swapped (A-phase on B-phase terminal, for
example)
Two PT secondary leads are swapped (A-phase on B-phase terminal, for
example)
NOTE: In either case, the phase input that is not swapped will read normal lagging power
factor.
Table C– 14:Section IV—Case F
Symptoms: 4-Wire Possible Causes
kW = negative and less than kVAR
KVAR = negative and close to value expected for kW
kVA = expected value
Power factor low and leading
Voltages and currents are normal
All three PT lead connections “rotated” counterclockwise: A-phase wire on
C-phase terminal, B-phase wire on A-phase terminal, C-phase wire on B-
phase terminal.
All three CT lead connections “rotated” clockwise: A-phase wire on B-phase
terminal, B-phase wire on C-phase terminal, C-phase wire on A-phase
terminal.
Table C– 15:Section IV—Case G
Symptoms: 4-Wire Possible Causes
kW = negative and less than kVAR
kVAR = positive and close to the value for kW
NOTE: looks like kW and kVAR swapped places
kVA = expected value
Power factor low and lagging
Voltages and currents are normal
All three PT lead connections “rotated” clockwise: A-phase wire on B-phase
terminal, B-phase wire on C-phase terminal, C-phase wire on A-phase
terminal.
All three CT lead connections “rotated” counterclockwise: A-phase wire on
C-phase terminal, B-phase wire on A-phase terminal, C-phase wire on B-
phase terminal.