Basic Functional Test - Single Inverter
975-0239-01-01 2–33
This manual for use by qualified personnel only
Enable the Inverter
By default, Invert Mode is enabled and the unit should start inverting upon
transitioning from Standby Mode. If Invert Mode is disabled, the display will show
(---) once out of Standby Mode. If the unit powers up in Standby Mode, press the
O
N/OFF button momentarily to change the mode from Standby to Operating.
To enable the inverter:
Press the inverter ON/OFF button and the Equalize button at the same time.
“En” is briefly displayed on the inverter panel to indicate the inverter is
enabled.
To disable the inverter:
Press the inverter ON/OFF button and the Equalize button at the same time.
“diS” is briefly displayed on the inverter panel to indicate the inverter is
disabled.
CAUTION: Equipment Damage
Prior to activating the inverter, ensure that all AC loads are disconnected from the
output of the inverter.
Figure 2-23 Enable the Inverter
ON/OFF
Button
All LEDs temporarily illuminate.
Briefly press the Equalize Button and the O
N/OFF Button at the same time
to enable or disable the Invert Mode.
Equalize
Button
ON/OFF
Button
Equalize
Button
This display indicates the
inverter is disabled.