Installing the Network
975-0239-01-01 3–7
This manual for use by qualified personnel only
Guidelines for Routing the Xantrex Xanbus Cables
To ensure maximum performance of your network, follow these guidelines when
routing the Xantrex Xanbus cables.
Route the cables away from sharp edges that might damage the insulation.
Avoid sharp bends in the cable—no less than a 4-inch (100 mm) radius.
Allow at least 2 ¼ inches (57 mm) of space behind the wall to accommodate
the depth of the unit and allow room for the cables to bend.
Allow for some slack in the cable tension.
Keep the alignment of wire pairs inside the sheath as straight as possible.
Allow separation between data and power cables (data cables should only
cross a power cable at right angles).
Do not staple the cable with metal cable staples. Use appropriate hardware
fasteners to avoid damage to the cable.
Support horizontal cables using J hooks or cable trays.
The total length of the network, including all connected Xantrex Xanbus-enabled
devices and the Xantrex XW Series, cannot exceed 130 feet (40 m).
:
WARNING: Shock hazard
Do not route the Xantrex Xanbus cables in the same conduit or panel as the AC
and DC power cabling.