Additional Adjustment Parameters for Variable Torque
Table 9 lists the additional parameters that are accessible when the
macro-configuration is set to Variable Torque.
Table 9: 2—Additional Adjustment Parameters with
Variable Torque Macro-Configuration
[1]
Parameter Code Description
Adjustment
Range
Factory
Setting
DC Inj.Curr.- A IdC
DC injection braking current
level. This parameter is
accessible if a logic input is
assigned to DC injection
braking. After 30 seconds, IdC is
automatically set to 0.5 ItH if
previously set to a higher value.
0.10 to 1.36
of I
n
[2]
Varies
according
to drive
controller
size.
NOTE: V/f Profile
is available only if
the energy savings
function (nld) is set
to No.
V/f Profile - % PFL
Volts/Hertz adjustment 0 to 100% 20%
This function is available in variable torque mode and if the
Energy Economizer (Energy Savings) function (nld) is
disabled.
This parameter is useful in applications where the user
wishes to define the volts/hertz profile manually instead of
having the drive controller perform this function with the
Energy Economizer function. The 100% setting provides a
linear V/Hz output from 0–FrS (nominal motor frequency).
[1]
On the 125–500 hp drive controllers, Preset Speeds and Jog are also available. See
Tables 7 and 8 for descriptions of these functions. IR Compensation appears on 125–
500 hp drive controllers if the Special Motor parameter, SPC, is set to Yes in Menu 3.
[2]
I
n
= drive controller constant torque output current rating shown on the drive controller
nameplate.