VVDED397047USR6/03 Chapter 2—Menus
06/2003 5—I/O Menu
83
maximum configured value of the analog output (AOH) corresponds
to 200% of the nominal motor torque.
Signed Motor Torque
When configured for signed motor torque (Stq), the analog output
provides a signal proportional to motor or braking torque. Zero torque
corresponds to:
(AOL + AOH)/2
The minimum configured value (AOL) corresponds to 200% braking
torque while the maximum configured value of the analog output
(AOH) corresponds to 200% of the nominal torque.
Signed Ramp
When configured for signed ramp output, ORS, the analog output
provides a signal proportional to the frequency the drive controller is
commanding the motor to run in the reverse or forward direction. Zero
frequency corresponds to:
(AOL+AOH) / 2
The minimum configured value, AOL, corresponds to the maximum
frequency (tFr) in the reverse direction, while the maximum
configured value, AOH, corresponds to the maximum frequency (tFr)
in the forward direction.
PI Setpoint
When configured for PI setpoint, OPS, the analog output provides a
signal proportional to the PI setpoint being provided to the drive
controller. The minimum configured value, AOL, corresponds to the
minimum setpoint, while the maximum configured value, AOH,
corresponds to the maximum setpoint.
PI Feedback
When configured for PI feedback, OPF, the analog output provides a
signal proportional to the PI feedback being provided to the drive
controller. The minimum configured value, AOL, corresponds to the
minimum feedback, while the maximum configured value, AOH,
corresponds to the maximum feedback.