VVDED397047USR6/03 Chapter 2—Menus
06/2003 3—Drive Menu
49
Trq.Limit1 -%
[4]
tLI
Torque limit allows limitation of
the maximum motor torque.
0 to 200%
torque
200%
Int.I Lim -A CLI
Current limit used to limit the
maximum motor heating.
0 to 1.36 of I
n
[2]
1.36 of I
n
[2]
Auto DC Inj. AdC
Allows deactivation of automatic
DC injection at stop.
No - Yes Yes
NOTE: Mot P
Coef. is only
available if motor
switching is
enabled.
Mot P Coef. PCC
Defines the ratio between the
nominal drive controller power
and the motor with the lowest
power rating when a logic input
is assigned to the motor
switching function (see
page 71).
0.2 to 1 1
NOTE: Modifying
SFt causes the
following
parameters to
revert to factory
settings:
3—Drive Menu:
nCr, CLI, SFr, nrd
2—Adjust Menu:
itH, IdC, Ibr, Ctd
Sw. Freq. Type SFt
Allows selection of the type of
switching frequency.
LF - HF1 -
HF2
[5]
LF
LF allows adjustment between 0.5 and 4 kHz using the
SFr parameter.
HF1 and HF2 allow adjustment between 4 and 16 kHz:
HF1 is for applications with a low duty cycle, without
derating the drive controller. If the drive controller
thermal state goes above 95%, the switching frequency
automatically goes to 2 or 4 kHz (depending on rating).
When the thermal state returns to 70%, the switching
frequency returns to the set value.
HF2 is for machines with a high duty cycle with derating
of the drive controller by one power rating. The drive
parameters (current limit, thermal current, etc.) are
automatically scaled.
Table 11: 3—Drive Menu Parameters (continued)
Parameter Code Description
Adjustment
Range
Factory
Setting
[1]
Depending on the position of the 50/60 Hz switch. Ensure that the switch setting
matches the input frequency (see page 14).
[2]
I
n
= drive controller constant torque output current rating shown on the drive controller
nameplate.
[3]
The factory setting depends on the macro-configuration used: No for Material
Handling, Yes for General Use and Variable torque.
[4]
This parameter is not available on 125–500 hp drive controllers.
[5]
Refer to the drive controller instruction bulletin, VVDED397048US, for duty cycle
ratings of the drive controllers.
These parameters are available only with the I/O extension card installed.