VVDED397047USR6/03 Chapter 2—Menus
06/2003 3—Drive Menu
41
3—Drive Menu
This menu is accessible when the access locking switch is in the total
unlock, , position. The parameters can only be modified when the
motor is stopped.
Curr.Lev.Att- A Ctd
Current threshold above which
the logic output or relay goes to
state 1.
0.25 to 1.36
of I
n
[3]
1.36 of
I
n
[3]
ThermLevAtt - % ttd
Motor thermal state threshold
above which the logic output or
relay goes to state 1 (high).
0 to 118% 100%
Torque lim2 -A
[4]
tL2
Second torque limit, activated by
a logic input.
0% to
200%
[2]
200%
DC Inj. Curr. -A IdC
DC injection braking current
level.
Accessible if a logic input
is assigned to DC injection
braking. After 30 s, IdC is
automatically set to 0.5 ItH if
previously set to a higher value.
0.10 to 1.36
of I
n
[3]
0.7 ItH
Accelerate 2- s
Decelerate 2- s
AC2
dE2
Second acceleration and
deceleration ramp times. These
parameters are accessible if a
logic input is assigned to ramp
switching or if Frt is not 0.
0.05 to 999.9 5 s
TachFBCoeff ★ dtS
Tachometer scaling factor
associated with the tachometer
feedback function:
1 to 2 1
Table 10: 2—Additional Adjustment Parameters After I/O
Reassignment (continued)
Parameter Code Description
Adjustment
Range
Factory
Setting
[1]
Depending on the position of the 50/60 Hz switch.
[2]
100% corresponds to the nominal torque of a motor with horsepower size equal to that
of the drive controller at its constant torque rating.
[3]
I
n
= drive controller constant torque output current rating shown on the drive controller
nameplate.
[4]
This parameter is not available on 125–500 hp drive controllers.
★ These parameters are available only with the I/O extension card installed.
Menu
2
dtS
9
tachometer voltage at HSP
-----------------------------------------------------------------------
=