© 1998–2003 Schneider Electric All Rights Reserved
VVDED397047USR6/03 Chapter 2—Menus
06/2003 5—I/O Menu
71
Fast Stop
Fast stop is a braked stop with the deceleration ramp time reduced by
a programmable coefficient (see dCF on page 48). Fast stop is
obtained by opening the logic input assigned to the function (setting it
to state 0), or by configuring fast stop (Fst: Fast Stop) under type of
stop (Stt on page 47).
Motor Switching
This function allows a single drive controller to control two motors with
different power ratings, one at a time. The ratio between the motor
power ratings is set with the PCC parameter in the 3
—Drive menu
(see page 49).
If the two motors have different power ratings, enclosure types, or
speed ratings, then separate motor contactors, thermal protection,
and short circuit protection will be required for each motor. This
function automatically inhibits motor thermal protection of the
second motor.
The motor switching command will not be taken into account unless
the motor is stopped. If the output contactor opens while the motor is
running, the drive controller may trip on overcurrent or overvoltage
which may result in damage to the drive controller. The following
WARNING
EXTENDED STOPPING TIME
• Deceleration time during fast stop may be automatically
extended depending on the braking ability of the drive controller.
• A dynamic brake or mechanical stopping/holding brake may be
required for consistent stopping times independent of motor load
conditions.
• Fast stop does not function during loss of power or drive
controller fault.
Failure to follow these instructions can result in death, serious
injury, or equipment damage.