VVDED397047USR6/03 Chapter 2—Menus
06/2003 5—I/O Menu
73
External Fault
Assigning a logic input to External Fault allows an external contact
closure to stop the drive controller and motor. The stop type is
determined by the configuration of the Stt parameter (Type of Stop) in
the 3—Drive menu.
Force to Local
Permits going from serial link command to local command using the
keypad display or terminal strip, depending on the setting of the LCC
parameter in the 4Control menu. Assigning this parameter selects a
local command when the logic input is closed (state 1).
Auto-tuning
When the assigned logic input changes to 1 an auto-tuning operation
is triggered, as parameter TUN is described on page 45 in the 3
Drive menu.
Auto tuning is only performed if no command has been activated. If a
Freewheel Stop or Fast Stop function is assigned to a logic input, this
input must be set to 1 (active at 0).
Encoder Inputs
(Only with an I/O extension card with encoder input, VW3A58202U)
Speed Regulation
The inputs can be used to connect an encoder for improving speed
regulation in applications where the load is changing. To program the
encoder speed feedback, configure AI3 in the 5
I/O menu for RGI,
Encoder Feedback. Then configure the encoder type and number of
pulses in the 3
Drive menu.
The A, A-, B, and B- inputs on the I/O option card are for use in
forward and reverse directions.
The A input can also be used with an inductive sensor or a
photoelectric detector for simplified, but less accurate regulation.
Summing Speed Reference
The setpoint from the encoder input is summed with AI1.