ALTIVAR
58 Keypad Display VVDED397047US R8/01
Chapter 2 Menus 08/01
26
© 19982001 Schneider Electric All Rights Reserved
1DISPLAY MENU
Display parameters can be viewed in any access level. You can scroll
through these parameters with the motor running.
Table 5: 1Display Menu Parameters
Parameter Code Function Units
Drive. state
Use this parameter
to monitor drive
controller status.
rdY
rUn
ACC
dEC
CLI
dCb
nSt
Obr
Drive controller status: indicates a fault or the state
of the drive controller:
rdY = drive controller is ready
rUn = motor in steady state
ACC = accelerating
dEC = decelerating
CLI = in current limit
dCb = DC injection braking
nSt = commanded to freewheel stop
Obr = braking with deceleration ramp adaptation
Freq. Ref. - Hz
FrH
Reference frequency Hz
Output Freq. - Hz
rFr
Output frequency applied to the motor Hz
Motor Speed - RPM
SPd
Motor speed estimated by the drive controller.
Based on nominal motor speed (nSP) entry. See
Table 11 on page 39.
RPM
Motor Current - A
LCr
Motor current A
Machine Spd.
USp
Machine speed estimated by the drive controller.
USP is proportional to rFr scaled by the coefficient,
USC, which is adjustable in the 2Adjust menu.
Output Power - %
Opr
Output power estimated by the drive controller.
100% corresponds to nominal power.
%
Mains Voltage V
ULn
Mains voltage V
Motor Thermal - %
tHr
Thermal state: 100% corresponds to the nominal
motor thermal state. Above 118%, the controller
trips on OLF (motor overload fault).
%
Drive Thermal - %
tHd
Thermal state of the drive controller: 100%
corresponds to the nominal drive controller thermal
state. Above 118%, the controller trips on OHF
(drive overheating fault). It resets when the thermal
state goes below 70%.
%
Last Fault
LFt
Displays the last fault which occurred
Freq. Ref
LFr
This adjustment parameter appears in place of the
FrH parameter when command of the drive
controller by the keypad display has been activated
with the LCC parameter in the 4Control menu
(see page 49).
Hz
Consumption
APH
Energy consumed kWh or
MWh
Run time
rtH
Operating time (motor powered up) in hours. hrs
Menu
1
Note: If USP is
greater than
9999, the display
value is
USP/1000.