ALTIVAR
58 Keypad Display VVDED397047US R8/01
Chapter 2 — Menus 08/01
46
© 1998–2001 Schneider Electric All Rights Reserved
Table 13: 4—Control Menu: 2-Wire Control Type
Parameter Code Description
Adjustment
Range
Factory
Setting
Type 2 Wire
tCt
Defines the type of 2-wire control: LEL-TrN-
PFW
LEL
• LEL: If the forward or reverse input is high when the drive
controller is powered up, the drive controller will start the
motor. If both inputs are high on power up, the controller will
run forward.
• TrN: The drive controller must see a transition from low to high
of the forward or reverse input before it will start the motor.
Therefore, if the forward or reverse input is high when the drive
controller is powered up, the input must be cycled before the
drive controller will start the motor.
• PFW: Forward input has priority over reverse input with this
control. If forward is activated while the controller is running in
reverse, the controller will run forward.
2-wire control wiring example:
RV inhibit
rln
When configured for Yes, this function
inhibits reverse operation even if
Yes - No No
reverse operation is requested by a summing or PI regulator
function. This parameter is not available if a logic input is
configured for reverse. A logic input cannot be configured for
reverse if this parameter is configured for Yes.
Menu
4
NOTE: Type 2
Wire appears if
2-wire control is
selected.
ATV58 terminal strip
24 V LI1 LIx
LI1: Forward
LIx: Reverse
Komentáře k této Příručce