Chapter 2 Menus 08/01
72
© 19982001 Schneider Electric All Rights Reserved
Using the Analog Outputs on the I/O Extension Cards
The analog outputs on the Analog I/O and Digital I/O extension cards are
current outputs. The minimum and maximum values (AOL and AOH
parameters) are configurable, each with a range of 020 mA.
Figure 20: I/O Extension Card Minimums and Maximums
Motor Current
When configured for motor current (OCr), the analog output provides a
signal proportional to motor current. The minimum configured value
corresponds to zero while the maximum configured value of the analog
output corresponds to 200% of the drive controllers constant torque
rating.
Output Frequency
When configured for output frequency (OFr), the analog output provides
a signal proportional to the motor frequency estimated by the drive
controller. The minimum configured value corresponds to zero while the
maximum configured value of the analog output corresponds to the
maximum frequency setting, not the high speed setting.
Ramp Output
When configured for ramp output (OrP), the analog output provides a
signal proportional to the frequency the drive controller is commanding
the motor to run. The minimum configured value (AOL) corresponds to
zero while the maximum configured value of the analog output (AOH)
corresponds to the maximum frequency setting (tFr), not the high speed
setting.
(mA)
0
Max.
Min.
0 mA 20 mA
20 mA maximum4 mA minimum