ALTIVAR
58 Keypad Display VVDED397047US R8/01
Chapter 2 Menus 08/01
48
© 19982001 Schneider Electric All Rights Reserved
Table 14: 4Control Menu: Other Parameters
Parameter Code Description
Adjustment
Range
Factory
Setting
AI2 min Ref.-mA
AI2 Max. Ref-mA
CrL
CrH
CrL: Minimum value of the signal on
analog input AI2
CrH: Maximum value of the signal
on analog input AI2
These two parameters allow definition
of the signal at AI2. The input can be
configured for 020 mA, 420 mA,
204 mA, among other possibilities.
CrL: 020
mA
CrH:
420 mA
CrL: 4 mA
CrH:
20 mA
AO min Val-mA
AO Max. Val-mA
AOL
AOH
Min. value of the signal on output AO
Max. value of the signal output on AO
These two parameters are used to
define the output signal on AO.
Eg. : 020 mA, 420 mA, 204 mA, etc.
020 mA
020 mA
0 mA
20 mA
Save Ref
Str
This function allows saving the
reference, either when the run
command is removed (RAM) or when
NO-RAM-
EEP
NO
mains power is removed (EEP). When the motor is next started,
the reference speed will be the last saved reference. In order for
speed reference to be saved in EEP mode, the run command
should not be present when re-applying power.
These parameters are available only with the I/O extension card installed.
Menu
4
Note: If CRL is set higher
than CRH, reverse sense
operation will result (i.e.,
20 mA will equal low speed
and 4 mA will equal high
speed).
AI 2
(mA)
0
LSP
HSP
CrL CrH 20
Frequency
AO (mA)
0
Max.
AOL AOH 20
Parameter
NOTE: Save
Reference is only
available if LIs are
assigned to
+Speed/-Speed.