Table 14: 4—Control Menu: Other Parameters
Parameter Code Description
Adjustment
Range
Factory
Setting
AI2 min Ref.-mA
AI2 Max. Ref-mA
CrL
CrH
• CrL: Minimum value of the signal on
analog input AI2
• CrH: Maximum value of the signal
on analog input AI2
These two parameters allow definition
of the signal at AI2. The input can be
configured for 0–20 mA, 4–20 mA,
20–4 mA, among other possibilities.
CrL: 0–20
mA
CrH:
4–20 mA
CrL: 4 mA
CrH:
20 mA
AO min Val-mA ★
AO Max. Val-mA ★
AOL
AOH
Min. value of the signal on output AO
Max. value of the signal output on AO
These two parameters are used to
define the output signal on AO.
Eg. : 0–20 mA, 4–20 mA, 20–4 mA, etc.
0–20 mA
0–20 mA
0 mA
20 mA
Save Ref
Str
This function allows saving the
reference, either when the run
command is removed (RAM) or when
NO-RAM-
EEP
NO
mains power is removed (EEP). When the motor is next started,
the reference speed will be the last saved reference. In order for
speed reference to be saved in EEP mode, the run command
should not be present when re-applying power.
★ These parameters are available only with the I/O extension card installed.
Menu
4
Note: If CRL is set higher
than CRH, reverse sense
operation will result (i.e.,
20 mA will equal low speed
and 4 mA will equal high
speed).
AI 2
(mA)
0
LSP
HSP
CrL CrH 20
Frequency
AO (mA)
0
Max.
AOL AOH 20
Parameter
NOTE: Save
Reference is only
available if LIs are
assigned to
+Speed/-Speed.