VVDED397047US R8/01 ALTIVAR
58 Keypad Display
08/01 Chapter 2 Menus
© 19982001 Schneider Electric All Rights Reserved
53
Table 16 shows which functions can be assigned to relay output R2, logic
output LO, and analog output AO.
Table 16: Possible Assignments for Configurable Outputs
I/O Extension Card
Logic
Output
LO
Analog
Output
AO
Drive Controller without an I/O Extension Module
Relay
R2
NO: Not assigned No assigned X X X
RUN: DriveRunning Drive controller running X X
OCC: Output Cont. Output contactor command X X
FTA: Freq Attain. Frequency threshold attained X X
FLA: HSP Attained High speed attained X X
CTA: I Attained Current level attained X X
SRA: FRH Attained Reference speed attained X X
TSA: Mtr Therm Lv1 Motor thermal level attained X X
APL:4-20 mA loss Loss of 420 mA signal X X
F2A:F2 Attained Second frequency threshold
reached
XX
BLC: Brk Logic Brake logic X
OCR: Motor current Motor current X
OFR: Motor Frequency Motor speed X
ORP: Output Ramp Ramp output X
OPS:PID ref. PID setpoint output, If one AI = PIF X
OPF:PID Feedback PID feedback output, If one
AI = PIF
X
OPE:PID Error PID error output, If one AI = PIF X
OPI:PID Integral PID integral output, If one AI = PIF X
OPR:Motor power Motor power X
THR: Motor Thermal Motor thermal state X
THD: Drive Thermal Drive thermal state X
TRQ: Motor torque Motor torque X
STQ: Signed Torq. Signed motor torque X
Menu
5