ALTIVAR
58 Keypad Display VVDED397047US R8/01
Chapter 2 Menus 08/01
60
© 19982001 Schneider Electric All Rights Reserved
Figure 16: +Speed Timing Diagram (Selector Switches)
Preset Speeds
2, 4, or 8 speeds can be preset, requiring 1, 2, or 3 logic inputs,
respectively.
Table 19 shows how the logic inputs are configured for Preset Speeds
and the input states that activate them.
Table 19: Preset Speed Logic
2 Preset Speeds 4 Preset Speeds 8 Preset Speeds
Assign LIx to PS2. Assign LIx to PS2, then LIy to
PS4.
Assign LIx to PS2, then LIy to PS4,
then LIz to PS8.
LIx Speed reference LIy LIx Speed reference LIz LIy LIx Speed reference
0 LSP + AI
reference
0 0 LSP + AI reference 0 0 0 LSP + AI reference
1 HSP 0 1 SP2 0 0 1 SP2
1 0 SP3 0 1 0 SP3
1 1 HSP 0 1 1 SP4
1 0 0 SP5
1 0 1 SP6
1 1 0 SP7
111HSP
Forward
LSP
LSP
0
0
0
2nd action
1st action
aaa a a a a
bb
cc
d
Reverse
2nd action
1st action
Motor
Frequency
NOTE: To reassign
the logic inputs to a
function other than
Preset Speeds,
PS8 (LIz) must be
cleared, then PS4
(LIy), then PS2
(LIx).