VVDED397047US R8/01 ALTIVAR
58 Keypad Display
08/01 Chapter 2 Menus
© 19982001 Schneider Electric All Rights Reserved
31
Jump Freq.2- Hz
JF2
Second skip frequency: same
function as JPF, for a second
frequency value.
0 to HSP 0 Hz
Jump Freq.3- Hz
JF3
Third skip frequency: same
function as JPF, for a third
frequency value.
0 to HSP 0 Hz
Machine Coef.
USC
Machine Speed Coefficient.
Coefficient applied to rFr
0.01 to 100.0 1.00
permitting the display of machine speed by the parameter USP.
USP = rFr x USC
LSP Time - s
tLS
Low speed run time. Following
operation at LSP for the amount
0.0 to 999.9 s 0
of time defined by tLS, the motor is automatically commanded
to stop. The motor restarts if the frequency reference is greater
than LSP, if a run command continues to be present. 0 means
that no time period is set.
Table 6: 2Fixed Set of Adjustment Parameters (Continued)
Parameter Code Description
Adjustment
Range
Factory
Setting
[1]
I
n
= drive controller constant torque output current rating shown on the drive
controller nameplate.