VVDED397047US R8/01 ALTIVAR
58 Keypad Display
08/01 Chapter 2 — Menus
© 1998–2001 Schneider Electric All Rights Reserved
49
KeypadCom.
LCC
Allows command of the drive controller
via the keypad display. The STOP/
RESET, RUN, and FWD/REV keys are
No - Yes No
active. The reference speed is given by the LFr parameter (see
page 28). Only the freewheel stop, fast stop,
and stop by DC injection commands remain active at the
terminal strip. If the link between the drive controller and keypad
display is lost, the drive controller will trip on the SLF fault (serial
link fault).
Stop Priorit.
PSt
This function gives priority to the STOP
key on the keypad display no matter
No - Yes Yes
what the command source (terminal strip, keypad display, or
serial link). To change the PSt parameter to No:
1. Display no.
2. Press ENT.
3. The drive controller displays “See manual”.
4. Press the up arrow key, then the down arrow key, then ENT,
then ESC.
When set to No, the stop key on the keypad display will be
inactive. To return to Yes, display Yes then press enter.
DriveAddress
Add
Drive controller address controlled
through the RS-485 port by a MODBUS
device (i.e., without the programming or
operating keypad display).
0 to 31 0
BdRate RS485
tbr
Transmission speed on the RS-485
MODBUS port on the front of the drive
controller.
4800 Bits / second
9600 Bits / second
19200 Bits / second
4800–
9600–
19200–
19200
Table 14: 4—Control Menu: Other Parameters
Parameter Code Description
Adjustment
Range
Factory
Setting
★ These parameters are available only with the I/O extension card installed.
Menu
4
DISABLED STOP COMMAND
Disabling the stop key on the keypad display will prevent the drive
controller from stopping when the stop key is pressed. An external
stop command must be installed to stop the motor.
Failure to follow this instruction can result in death, serious
injury, or equipment damage.
WARNING