Table 6: 2—Fixed Set of Adjustment Parameters
Parameter Code Description
Adjustment
Range
Factory
Setting
Freq. Ref. - Hz
LFr
Appears when drive controller
command from the keypad display
has been activated using the LCC
LSP to HSP
parameter in the 4—Control menu (see page 49).
Acceleration -s
Deceleration -s
ACC
dEC
Acceleration and deceleration
ramp times. Defined as time
between 0 and FRS.
0.05 to 999.9
0.05 to 999.9
3 s
3 s
Low Speed - Hz
LSP
Low speed
0 to HSP 0 Hz
High Speed - Hz
HSP
High speed. Ensure that this
adjustment is suitable for the
motor and the application.
LSP to tFr 50/60 Hz
depending
on switch
setting
Gain - %
FLG
Frequency loop gain. This
parameter allows adjustment of
0 to 100 20
the response time of the drive controller to sudden changes in
the motor load. Decreasing the gain parameter slows the
response time of the drive controller. Increasing the gain
parameter makes the drive controller respond more quickly.
This parameter should be increased in applications where the
undesirable changes in motor speed occur due to changes in
motor load. Applications that have fast cycle times or high
torque requirements may require an increase in gain.
Stability - %
StA
Frequency loop stability.
This parameter allows adjustment
of speed overshoot of the drive
0 to 100 20
controller to sudden changes in the motor load. Increasing the
stability setting dampens the overshoot. This parameter should
be adjusted with the gain setting to tune the drive controller
response to meet the desired performance on applications that
have fast cycle times or high torque requirements.
[1]
I
n
= drive controller constant torque output current rating shown on the drive
controller nameplate.