ALTIVAR
58 Keypad Display VVDED397047US R8/01
Appendix A—Drive Controller Configuration 08/01
98
© 1998–2001 Schneider Electric All Rights Reserved
The following tables list the factory setting for each parameter. The new
customer setting can be noted in the Customer Setting column. If no
change has been made to the factory setting, the customer can note “no
change” in the Customer Setting column.
Table 28: Menu 2—Adjustment Parameters
Code Fact. Setting Cust. Setting Code Fact. Setting Cust. Setting
ACC 3 s s SP5 25 Hz Hz
dEc 3 s s SP6 30 Hz Hz
LSP 0 Hz Hz SP7 35 Hz Hz
HSP 50 / 60 Hz Hz JOG 10 Hz Hz
FLG 20% % JGt 0.5 s s
StA 20% % brL 0 Hz Hz
ItH 0.9 of I
n
A Ibr 0 A A
IdC 0.7 ItH A brt 0 s s
tdC 0.5 s s bEn 0 Hz Hz
SdC Varies A bEt 0 s s
JPF 0 Hz Hz FFt 50/60 Hz Hz
JF2 0 Hz Hz rPG 1
JF3 0 Hz Hz rIG 1 / s / s
AC2 5 s s PSP 0.0 s s
dE2 5 s s FbS 0.1
tLS no no or s PIC no
USC 1 dtS 1
UFr 100% % Ctd 1.36 of I
n
A
SLP 100% % ttd 100% %
PFL 20% % tL2 200% %
SP2 10 Hz Hz Ftd 50/60 Hz Hz
SP3 15 Hz Hz F2d 50/60 Hz Hz
SP4 20 Hz Hz
Komentáře k této Příručce